Date Text
2022-04-12 13:49:193RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21061171
 4/19/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS SP-1.08 & SP-3.01: PLEASE SUBMIT THE
 MANUFACTURER?S SPECIFICATIONS FOR THE CARTRIDGE FILTER
 TO VERIFY NO BACKWASHING IS REQUIRED AND NO CHLORINATED
 WASTEWATER WILL BE DISCHARGED TO THE STORM DRAINAGE
 SYSTEM- SECS. 454.1.6.5.5.1 & 454.1.6.5.5.2 FBC B &
 SEC. 90-205 (1) WPB CODE OR ORDINANCES.
  
 2) A-253: THE OUTDOOR SHOWER DETAIL DOES NOT APPEAR TO
 MATCH THE DRAWING SHOWN ON THE RINSE SHOWER SUBMITTAL.
 THE SUBMITTAL IS FOR AN INDEPENDENT FOOT TOWER SHOWER
 STATION HOWEVER THE DRAWING SHOWS THE SHOWER CONTROL,
 HEAD AND SPRAYER ATTACHED TO THE EXTERIOR SIDE OF THE
 RESTROOM WALL- PLEASE CLARIFY. PLEASE PROVIDE AN
 EQUIPMENT SCHEDULE SHOWER VALVE, HEAD AND SPRAYER
 INDICATING THE MAKES AND MODELS- SEC. 107.2.1 WPB. IF
 THE RINSE SHOWER IS TO BE INSTALLED PLEASE INDICATE THE
 MODEL NUMBER ON THE PLAN. PLEASE NOTE THAT MODEL NOS
 564 & 565 ARE DESIGNATED AS ACCESSIBLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER