| 2021-11-09 17:09:32 | 11/09/21 2ND COMMERCIAL POOL REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. DONE AND CLEAR |
| | |
| | 2. UNDER LS-03, WOULD YOU PLEASE PROVIDE THE DISTANCE |
| | FOR THE ENTRY DOORS OF THE RESTROOMS THAT SHALL BE |
| | LOCATED WITHIN A 200-FOOT HORIZONTAL RADIUS OF THE |
| | NEAREST WATER'S EDGE PER THE 2020 FBC SEC. B |
| | 454.1.6.1SANITARY FACILITIES (EXCEPTION). |
| | |
| | 3. DONE AND CLEAR |
| | |
| | 4. DONE AND CLEAR |
| | |
| | 5. DONE AND CLEAR |
| | |
| | 6.SECOND REQUEST; SP-102: PROVIDE COMPLETE PLANS AND |
| | SPECIFICATIONS FOR INSTALLATION OF THE RINSE SHOWER |
| | (MDF MODEL 500)- SECTION 107.2.1 WPB & 606.2 FBC P. |
| | |
| | NEW COMMENTS; |
| | A. ON SHEET P-102A SHOWS A DIFFERENT LAYOUT FOR THE |
| | SHOWER IN S DIFFERENT LOCATION THAN A-102A. WOULD YOU |
| | PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. COULD NOT FIND THE SPECIFICATIONS FOR MDF MODEL 500. |
| | WOULD YOU PLEASE RESUBMIT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. ON SHEET P-102A, A FLOOR DRAIN IS SHOWN, BUT IF IT |
| | IS EXPOSED TO THE OUTSIDE, IT CANNOT GO INTO THE |
| | SANITARY SYSTEM PER CITY ORDNANCE SEC. 90-126(5). - |
| | PROHIBITIONS AND LIMITATIONS OF DISCHARGE. |
| | |
| | D. THE RUNOFF OF THE SHOWER NEEDS TO GO INTO A LOCATION |
| | THAT CAN BE COLLECTED AND DISPOSED OF. WOULD YOU PLEASE |
| | PROVIDE A DRAIN TO THE STORM DRAIN OR A SAFE DRAINING |
| | PLACE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. FAIR HOUSING ACT MANUAL COMPLIANCE: SHOW THE |
| | ACCESSIBLE ROUTE TO THE RINSE SHOWER AND PROVIDE |
| | ENLARGED DRAWINGS AND CUTS SHOWING THE LOCATIONS AND |
| | HEIGHTS OF SHOWERHEADS AND CONTROLS, AND COMPLIANCE |
| | DETAILS FOR SPACE ALLOWANCE, REACH RANGES, AND CONTROLS |
| | AND OPERATING MECHANISMS- REFER TO PAGES 2.10- 2.12 OF |
| | THE MANUAL. |
| | |
| | THE MDF MODEL 500 IS NOT THE ONE SHOWN IN DETAIL # 2 ON |
| | SHEET A-253. WOULD YOU PLEASE PROVIDE A DETAIL THAT HAS |
| | THE INFORMATION REQUESTED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 7. ON THE DETAIL, SP-108 SHOWS WHAT APPEARS TO BE THE |
| | REQUIRED MAKEUP WATER CONTROLLER (AUTO-FILL) AT THE |
| | COLLECTOR TANK. WOULD YOU PLEASE NOTE THAT SEPARATE |
| | PERMITS ARE NEEDED TO INSTALL THE DEVICES- SECTION |
| | 105.1 WPB? |
| | |
| | 8. ON SHEET SP-105, IT SHOWS NO LOCATIONS OF ALL ITEMS |
| | IN THE PIPING LEGEND- E, F, G, H, I, J, K, & L. WOULD |
| | YOU PLEASE REMOVE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 9. DONE AND CLEAR |
| | |
| | 10. DONE AND CLEAR |
| | |
| | 11. DONE AND CLEAR |
| | |
| | 12. DONE AND CLEAR |
| | |
| | 13. DINE AND CLEAR |
| | |
| | 14. DONE AND CLEAR |
| | |
| | 15. SP-108 & 301: ON THE PUMP CURVE FOR THE SELECTED |
| | PUMP AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION |
| | 454.1.6.5.4 FBC B. |
| | |
| | NEW COMMENT; WOULD YOU PLEASE IDENTIFY ON THE PUMP |
| | CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING |
| | INSTALLED ON THIS POOL, THIS IS NEEDED TO CONFIRM THE |
| | MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE |
| | ANSI/APSP/ICC 7 - 2015 SECS. 4.4.9, 4.4.9.1. |
| | |
| | 16. SECOND REQUEST; WOULD YOU PLEASE SUBMIT THE |
| | MANUFACTURER'S SPECIFICATIONS FOR RECIRCULATION AND |
| | TREATMENT EQUIPMENT, INCLUDING THE SAND FILTER, |
| | CHEMICAL STORAGE TANKS, CHEMICAL CONTROLLER, AND |
| | FEEDERS SHOWING THE EQUIPMENT CONFORMS WITH REQUIRED |
| | STANDARDS NSF/ANSI STANDARD 50, CIRCULATION SYSTEM |
| | COMPONENTS, AND RELATED MATERIALS FOR SWIMMING POOL, |
| | SPAS/HOT TUBS, DATED APRIL 2007- SECTION 454.1.6.5.1 |
| | FBC B. |
| | |
| | 17. THE GRATE SUBMITTAL SUPPLIED DOES NOT COMPLY WITH |
| | THE 2017 FBC SEC 454.1.6.5.10.2. MAIN DRAIN |
| | COVERS/GRATES SHALL COMPLY WITH THE REQUIREMENTS OF |
| | ANSI/APSP 16 AND THE WATER VELOCITY OF THIS SECTION. |
| | 18. SP-301: INCLUDE THE HOSE BIB IN THE EQUIPMENT |
| | SCHEDULE- SECTION 608.15.4.2 FBC P. |
| | |
| | IT SAYS TO REFER TO P-601 ON RESPONSE, AND THIS SHEET |
| | IS NOT PROVIDED. WOULD YOU PLEASE PROVIDE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 19) SP-108, 301: THE GAS WATER HEATER INSTALLATIONS, |
| | INCLUDING THE GAS PIPING, COMBUSTION AND VENTING PLANS, |
| | AND EQUIPMENT ROOM VENTILATION SYSTEM, SHALL BE |
| | REVIEWED UNDER SEPARATE PERMITS AND PLAN SUBMITTALS- |
| | SECTION 105.1, 107.2.1, AND 107.3.5.3.1 WPB. PLEASE |
| | NOTE THAT THE EQUIPMENT ROOM VENTILATION SHALL COMPLY |
| | WITH THE FBC BUILDING AND MECHANICAL CODES. |
| | |
| | PER THE RESPONSE, P-101A HAS NO VERBIAGE OF A SEPARATE |
| | PERMIT REQUIRED FOR GAS AND SHEET M-101A, NOT SUPPLIES. |
| | WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 20. DONE AND CLEAR |
| | |
| | 21. DONE AND CLEAR |
| | |
| | 22. NEW COMMENT: ON SHEET SP-103 THE ACCESSIBLE REST |
| | ROOM SHOWS NO ELEVATION TO ENTER THE RESTROOM BUT ON |
| | SP-1.01. SP-1.02, A-1.02A, A-1.02B IT SHOWS TWO STEPS. |
| | WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |