| Plan Review Notes For Permit 21061171 |
| Permit Number |
21061171 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-04-25 11:40:50 | PLEASE ADDRESS COMMENTS 2 AND 3 FROM PREVIOUS REVIEW | | | CYCLE. | | | | | | | | | | | | 2) SHEET M-101A: PLEASE PROVIDE THE INFORMATION FOR THE | | | INTAKE AND EXHAUST FOR THE POOL EQUIPMENT ROOM. | | | PESF-1,PESF-1A, PEEF-1,PEEF-1A,PEEF-2 AND THE CFM?S | | | BROUGHT IN THROUGH THE 24 INCH X 10 INCH INTAKE DUCT. | | | FBC 107.2.1 | | | | | | 3) SHEET M-101A: PLEASE PROVIDE THE SPECIFICATIONS FOR | | | THE CHLORINE SENSOR. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | | | | | | | |
|