Plan Review Notes For Permit 21061171
Permit Number 21061171
Review Stop M
Sequence Number 2
Notes
Date Text
2022-04-25 11:40:50PLEASE ADDRESS COMMENTS 2 AND 3 FROM PREVIOUS REVIEW
 CYCLE.
  
  
  
 2) SHEET M-101A: PLEASE PROVIDE THE INFORMATION FOR THE
 INTAKE AND EXHAUST FOR THE POOL EQUIPMENT ROOM.
 PESF-1,PESF-1A, PEEF-1,PEEF-1A,PEEF-2 AND THE CFM?S
 BROUGHT IN THROUGH THE 24 INCH X 10 INCH INTAKE DUCT.
 FBC 107.2.1
  
 3) SHEET M-101A: PLEASE PROVIDE THE SPECIFICATIONS FOR
 THE CHLORINE SENSOR. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  