| Plan Review Notes For Permit 21061171 |
| Permit Number |
21061171 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-17 09:11:22 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT- 21061171 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-253: PLEASE PROVIDE THE POOL STORAGE EXHAUST | | | DRAWING FOR THE LEVEL 02 POOL STORAGE ROOM. FBC 107.2.1 | | | | | | 2) SHEET M-101A: PLEASE PROVIDE THE INFORMATION FOR THE | | | INTAKE AND EXHAUST FOR THE POOL EQUIPMENT ROOM. | | | PESF-1,PESF-1A, PEEF-1,PEEF-1A,PEEF-2 AND THE CFM?S | | | BROUGHT IN THROUGH THE 24 INCH X 10 INCH INTAKE DUCT. | | | FBC 107.2.1 | | | | | | 3) SHEET M-101A: PLEASE PROVIDE THE SPECIFICATIONS FOR | | | THE CHLORINE SENSOR. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|