| Plan Review Notes For Permit 21061149 |
| Permit Number |
21061149 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-23 08:04:17 | PLAN REVIEW ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: NOTE FROM ENGINEER OF RECORD (EOR) STATES NO | | | CHANGES SHALL BE MADE TO PLANS WITHOUT HIS APPROVAL. | | | | | | 1. REVISE PG E4. TO REFLECT PROPOSED CHANGES UNDER GEN | | | RES PERMIT 21060873. ( REPLACE GENERAC 48KW GEN WITH | | | KOHLER 100KW GEN, REMOVE LOAD SHEDDING FROM | | | CALCULATIONS, CHANGE CONDUCTOR SIZING FOR GEN TO PANEL | | | FROM 3 #300MCM TO 3 4/0, ATS WILL BE 400A SE, SHOW | | | CONTROL CIRCUT CONDUCTOR TYPE AND SIZING). | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PLAN PAGE E-1 AND ELECTRICAL SITE PLAN SHOW STANDBY | | | GENERATOR OUTSIDE GARAGE. GENERATOR LOCATION SHALL BE | | | PER PERMIT 21060873 (GEN-RES). REDLINED PLANS. | | | | | | NOTICE: REVISED PLAN PAGE E4 WILL REQUIRE VALID DIGITAL | | | SIGNATURE. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|