| 2022-09-21 11:17:21 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE WINDOW AND DOOR SCHEDULE ON SHEET S-1 HAS A |
| | FIXED WINDOW AND THE PRODUCT APPROVALS THAT WERE |
| | SUBMITTED ARE FOR A HORIZONTAL ROLLING WINDOW. PLEASE |
| | CORRECT. FBC 107.2.1 |
| | |
| | 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | HORIZONTAL ROLLING WINDOW AND THE SLIDING GLASS DOOR DO |
| | NOT SHOW THAT THEY ARE IN COMPLIANCE WITH THE 2020 FBC. |
| | THEY ARE ALSO REQUIRED TO BE APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. FBC AMEND. 107.3.4 - PROVIDE TWO |
| | SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE |
| | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING |
| | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES |
| | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW |
| | (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR |
| | TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED ON THE |
| | PLANS, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND |
| | APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE |
| | INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR |
| | ELECTRONICALLY SUBMITTED DOCUMENTS. |
| | |
| | 3) SUBMIT PRODUCT APPROVALS FOR THE CONCRETE ROOF TILE |
| | AND TILE ADHESIVE ( IF USED ), THAT HAVE BEEN REVIEWED |
| | AND APPROVED BY THE DESIGNER OF RECORD. SPECIFY THE |
| | METHOD THAT WILL BE USED TO ATTACH THE TILE. FBC AMEND. |
| | 107.3.4 |
| | |
| | 4) SUBMIT ENERGY CODE COMPLIANCE FORMS. FBC ENERGY |
| | COMPLIANCE CHAPTER 4 [RE] RESIDENTIAL ENERGY |
| | EFFICIENCY. PLANS SPECIFY THE ADDITION AS A FAMILY ROOM |
| | AND IT MAY BECOME CONDITIONED SPACE IN THE FUTURE. |
| | THEREFORE IT NEEDS TO BE INSULATED. |
| | |
| | 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |
| | |