| 2021-07-30 08:24:45 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PLANS SPECIFY THIS PROJECT AS BEING EXPOSURE |
| | CATEGORY B. THE DEFAULT EXPOSURE CATEGORY IS C. DUE TO |
| | THE OPEN AREAS OF THE GOLF COURSE, THE LAKES AND CANALS |
| | THAT ARE IN CLOSE PROXIMITY TO THE PROJECT SHOULD BE |
| | CONSIDERED EXPOSURE CATEGORY C. IF YOU DISAGREE, |
| | PROVIDE AN ANALYSIS OF ALL OF THE WIND DIRECTIONS AT |
| | THE PROJECT THAT WILL SUPPORT YOUR DETERMINATION. |
| | FBC-R301.2.1.4 EXPOSURE CATEGORY |
| | |
| | 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | HORIZONTAL ROLLING WINDOW AND THE SLIDING GLASS DOOR DO |
| | NOT SHOW THAT THEY ARE IN COMPLIANCE WITH THE 2020 FBC. |
| | THEY ARE ALSO REQUIRED TO BE APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. FBC AMEND. 107.3.4 - PROVIDE TWO |
| | SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE |
| | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING |
| | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES |
| | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW |
| | (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR |
| | TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED ON THE |
| | PLANS, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND |
| | APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE |
| | INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR |
| | ELECTRONICALLY SUBMITTED DOCUMENTS. |
| | |
| | 3) SUBMIT PRODUCT APPROVALS FOR THE METAL ROOFING THAT |
| | HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF |
| | RECORD. FBC AMEND. 107.3.4 |
| | |
| | 4) SHOW COMPLIANCE WITH FBC-R806 FOR ROOF VENTILATION. |
| | |
| | 5) SPECIFY THE ROOF COMPONENT AND CLADDING PRESSURES ON |
| | THE PLANS. R301.2.1 WIND DESIGN CRITERIA |
| | |
| | 6) PROVIDE A FLASHING DETAIL FOR NEW METAL ROOF TO THE |
| | EXISTING GABLE WALL. FBC-R903.2 FLASHING |
| | |
| | 7) SUBMIT ENERGY CODE COMPLIANCE FORMS. FBC ENERGY |
| | COMPLIANCE CHAPTER 4 [RE] RESIDENTIAL ENERGY EFFICIENCY |
| | |
| | 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |
| | |