| 2021-07-06 14:34:59 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT REVISON- 21061047 |
| | 7/6/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 6TH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE 6TH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) AS NOTED IN THE APPROVED PLANS, THE IRRIGATION |
| | SYSTEM IS BE UNDER A SEPARATE PERMIT, HOWEVER THE PLANS |
| | APPEAR TO SHOW RUNOFF FROM THE IRRIGATION COLLECTED BY |
| | FLOOR DRAINS AND DRAINING INTO THE CITY SANITARY SEWER |
| | SYSTEM. PLEASE REVIEW SECTIONS 90-126 AND 90-203 & |
| | 90-205 WPB CODE OF ORDINANCES. BASED ON THOSE SECTIONS |
| | IT APPEARS THE IRRIGATION DRAINAGE IS PROHIBITED FROM |
| | DRAINING INTO THE SANITARY. PLEASE PROVIDE ADDITIONAL |
| | INFORMATION ABOUT THE IRRIGATION SYSTEM AND WHAT THE |
| | CONTENT OF THE IRRIGATION WASTEWATER IS. PLEASE SEE |
| | SEC. 90-126 FOR AN ITEMIZED LIST OF SANITARY SEWER |
| | PROHIBITIONS, AND ALSO THE COPIED FBC P SECTIONS BELOW. |
| | 701.4 SEWAGE TREATMENT. |
| | SEWAGE OR OTHER WASTE FROM A PLUMBING SYSTEM THAT IS |
| | DELETERIOUS TO SURFACE OR SUBSURFACE WATERS SHALL NOT |
| | BE DISCHARGED INTO THE GROUND OR INTO ANY WATERWAY |
| | UNLESS IT HAS FIRST BEEN RENDERED INNOCUOUS THROUGH |
| | SUBJECTION TO AN APPROVED FORM OF TREATMENT. |
| | 701.5 DAMAGE TO DRAINAGE SYSTEM OR PUBLIC SEWER. |
| | WASTE DETRIMENTAL TO THE PUBLIC SEWER SYSTEM OR TO THE |
| | FUNCTIONING OF THE SEWAGE-TREATMENT PLANT SHALL BE |
| | TREATED AND DISPOSED OF IN ACCORDANCE WITH SECTION 1003 |
| | AS DIRECTED BY THE CODE OFFICIAL. |
| | 703.4 EXISTING BUILDING SEWERS AND DRAINS. |
| | EXISTING BUILDING SEWERS AND DRAINS SHALL CONNECT WITH |
| | NEW BUILDING SEWER AND DRAINAGE SYSTEMS ONLY WHERE |
| | FOUND BY EXAMINATION AND TEST TO CONFORM TO THE NEW |
| | SYSTEM IN QUALITY OF MATERIAL. THE CODE OFFICIAL SHALL |
| | NOTIFY THE OWNER TO MAKE THE CHANGES NECESSARY TO |
| | CONFORM TO THIS CODE. |
| | |
| | 2) SHEET P1: IT APPEARS THE TRENCHING DIAGRAM DOES NOT |
| | INCLUDE THE EXTENDED TRENCH REQUIRED FOR THE MOST |
| | UPSTREAM RELOCATED FLOOR DRAIN- SECTION 107.2.1 WPB. |
| | |
| | 3) P1 & P2: REFER TO TABLE 909.1 FBC P AND INDICATE THE |
| | DISTANCE FROM THE RELOCATED FLOOR TRAPS TO THE VENTS. |
| | PLEASE INDICATE THE SIZES OF THE FD FIXTURE DRAINS. |
| | |
| | 4) P1 & P2: PLEASE SHOW TRAP PRIMER LINE RUNS AND A |
| | TRAP PRIMER INSTALLATION DETAIL- SECTION 1002.4.1.1 FBC |
| | P. |
| | |
| | 5) P2: PLEASE PROVIDE A DEDICATED FULL OPEN SHUT OFF |
| | VALVE FOR THE POINT OF USE WATER HEATER- SECTIONS 503.1 |
| | & 606.1(8) FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |