| 2021-07-06 15:32:16 | 07/06/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE KITCHEN SINK HAS BEEN MOVED TO A DIFFERENT |
| | LOCATION. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER |
| | DIAGRAM FOR SANITARY AND WATER PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | 2. THE NEW BAR SINK AND KITCHEN CANNOT DISCHARGE INTO |
| | THE WET VET OF A BATHROOM GROUP IT MUST BE DOWNSTREAM |
| | PER THE 2020 FBC SECTION R3108.1 HORIZONTAL WET VENT |
| | PERMITTED. |
| | |
| | 3. THE REFRIGERATOR IS IN A FIRE WALL; PLEASE PLACE A |
| | NOTE IF IN FIRE WALL THAT IT WILL REQUIRE TO BE FIRE |
| | RATED OR SHOW ON SIDE WALL WHICH DOES NOT REQUIRE RATED |
| | PROTECTION PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |