| Plan Review Notes For Permit 21061009 |
| Permit Number |
21061009 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-01 18:15:05 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | RISER AND PANEL SCHEDULE DON'T MATCH 215.5 | | | | | | PANEL "A" STATES 200A MAIN IN ONE PLACE AND 150A IN | | | ANOTHER, IF IT IS 200A 1/0 CONDUCTORS ARE NOT LARGE | | | ENOUGH TO FEED A 200A BREAKER. |
|