Notes
Date Text
2021-07-29 16:36:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS:
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 1. ACCESSIBILITY; SEE A08.01/DETAIL 3:
 A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
  
 2.034-P01_00 W G PIPINING PLAN DEMO AND G PIPINING PLAN
 DEMO APPEAR TO BE DUPLICATES OF EACH OTHER. PER WPB FBC
 107.2.1, PLEASE CLARIFY AND REMOVE ANY DUPLICATE PLAN
 SHEETS TO AVOID CONFUSION.
  
 3.035-P01_01 W G PIPING PLAN AND G PIPING PLAN APPEAR
 TO BE DUPLICATES OF EACH OTHER. PER WPB FBC 107.2.1,
 PLEASE CLARIFY AND REMOVE ANY DUPLICATE PLAN SHEETS TO
 AVOID CONFUSION.
  
 4.036-P01_02 W G PIPING ISOMETRIC PLAN AND G PIPING
 ISOMETRIC APPEAR TO BE DUPLICATES OF EACH OTHER. PER
 WPB FBC 107.2.1, PLEASE CLARIFY AND REMOVE ANY
 DUPLICATE PLAN SHEETS TO AVOID CONFUSION.
  
 5. REGARDING P01.01 WATER AND GAS PIPING PLAN AND
 P01.02 WATER AND GAS PIPING ISOMETRIC:
 KEYNOTE 7 STATES ?ADJUST AS REQUIRED AND RECONNECT
 EXISTING HOT WATER TANK?. I CANNOT FIND ON THE PLANS
 WHERE THIS APPLIES. PER WPB FBC 107.2.1, INDICATE NOTE
 7 ON THE PLANS OR IF IT DOES NOT APPLY, DELETE IT.
  
 6. REGARDING P01.00 WATER AND GAS DEMO PLAN:
 A.PER WPB FBC 107.2.1, PROVIDE KEYNOTE ADDRESSING
 REMOVAL OF CW TO CHILLER AND REMOVAL OF CHW AND
 INDICATE ON THE PLAN.
 B.I CANNOT FIND ON THE PLANS KEYNOTES 1, 4, 5, 6, 7, 8,
 9, 10, 15, 16 AND 17. PER WPB FBC 107.2.1, INDICATE ON
 THE PLANS OR IF A NOTE DOES NOT APPLY, DELETE IT.
 KEYNOTE 17 SPECIFICALLY ADDRESSES FW TO EXISTING
 MISTING CABINET. THERE IS A NOTE ON PLAN AT EXISTING
 PRODUCE CABINETS REGARDING MISTING WITHOUT A KEYNOTE
 DESIGNATION. PER WPB FBC 107.2.1, CLARIFY. INDICATE
 NOTE 17 ON THE PLANS OR IF IT DOES NOT APPLY, DELETE
 IT.
  
 7. REGARDING P02.00 SANITARY DEMO PLAN: .I CANNOT FIND
 ON THE PLANS KEYNOTES 1 THROUGH 18. PER WPB FBC
 107.2.1, INDICATE ON THE PLANS OR IF A NOTE DOES NOT
 APPLY, DELETE IT.
  
 8. REGARDING P02.01 SANITARY PIPING PLAN: KEYNOTE 4
 ADDRESSES P-2 AND D-3 IN THE ADDED FAMILY BATHROOM.
 PLUMBING FIXTURE AND DRAIN SCHEDULES DO NOT ADDRESS
 D-3. PER WPB FBC 107.2.2, CLARIFY AND RECONCILE
 DRAWINGS.
  
 9.PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 10. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21060925 8989 OKEECHOBEE BLVD
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved