| 2021-07-15 13:58:42 | RESIDENTIAL (R3) PORCH ADDITION, BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21060921 |
| | |
| | 1- BASED ON PLANS SUBMITTED THIS IS A PORCH ADDITION |
| | NOT JUST A DECK ADDITION. REVISE SCOPE OF WORK |
| | DESCRIPTION SPECIFIED ON THE PERMIT APPLICATION. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- INSULATED ROOF DETAIL ON SHEET S-3 IS A GENERIC |
| | DETAIL. |
| | A) ENGINEER OF RECORD NEEDS TO SPECIFY ALL FRAMING |
| | MEMBERS AND FASTENERS. ENGINEER TO SPECIFY BEAM SIZE, |
| | AND FASTENING TO THE COLUMNS. INSULATED PANEL SIZE AND |
| | FASTENERS TO THE BEAM AND TO THE EXISTING STRUCTURE. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | B) ENGINEER OF RECORD TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE " SCREEN WALL SYSTEM |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | C) SPECIFY ROOF SLOPE. SEC. R903.4 FBC-RESIDENTIAL. |
| | |
| | 3- SHEET S-1: |
| | A)NEW ALUMINUM POSTS SHOWN ON THE EXISTING 4" CONCRETE |
| | SLAB DON'T PROVIDE THE MINIMUM SIDECOVER CLEARANCE |
| | REQUIRED BY DETAIL S2. REVISE AS REQUIRED. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | B) THIS IS NOT AN ALTERATION LEVEL 3. THIS IS A PORCH |
| | ADDITION. REVISE INFORMATION AS REQUIRED. SEC. 606 |
| | FBC-EXISTING BUILDING. |
| | |
| | C)DESIGN CRITERIA SPECIFIES ASCE 7-10. THIS IS |
| | INCORRECT. THE CURRENT CODE 2020 FBC REFERENCES THE |
| | ASCE 7-16 NOT ASCE 7-10. REVISE AS REQUIRED. |
| | CHAPTER 553 F.S. |
| | |
| | 4- DETAIL 1/S-2 ON SHEET S-2: |
| | A)PROVIDE COMPLETE SPECIFICATIONS FOR ALUMINUM COLUMN. |
| | SPECIFY ALUMINUM THICKNESS AND FASTENING AT TOP AND |
| | BOTTOM. PROVIDE SPECIFICATIONS FOR WELDING OF ALUMINUM |
| | COLUMN TO BASE. SPECIFY TOP AND BOTTOM PLATE SIZE. |
| | NOTE: SPECIFY BASE PLATE FOR CORNER COLUMNS. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | B)THERE IS NOT EXISTING CONCRETE STEM WALL. REVISE |
| | FASTENING OF 2X8 WD. BEAM TO THE COLUMN PEDESTAL. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | C)THERE IS NOT EXISTING CONCRETE STEM WALL. REVISE |
| | FASTENING OF THE FLOATING DECK. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 5-DECK RAILING DETAILS ON SHEET S-2: SPECIFY FASTENER |
| | TYPE AND SIZE FOR EACH WOOD MEMBER. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 6-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR |
| | ALUMINUM PANELS SPECIFIED BY THE ENGINEER OF RECORD. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS |
| | UPDATED TO $10,000. THE PERMIT FEE BALANCE IS $154.62. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |