Plan Review Notes
Plan Review Notes For Permit 21060874
Permit Number 21060874
Review Stop B
Sequence Number 2
Notes
Date Text
2021-08-24 14:30:32RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWING G200 SHOWS THE ASSEMBLY AREA AS HAVING AN
 OCCUPANT LOAD OF 59 WHICH WILL REQUIRE 2 EXITS FROM
 THAT AREA - YOU CANNOT EXIT THRU A KITCHEN PER FBC
 1016.2 (5) EGRESS SHALL NOT PASS THROUGH KITCHENS,
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES.
 PLEASE RE CALCULATE THE ASSEMBLY AREA - FBC 1004.6
 FIXED SEATING.
 FOR AREAS HAVING FIXED SEATS AND AISLES, THE OCCUPANT
 LOAD SHALL BE DETERMINED BY THE NUMBER OF FIXED SEATS
 INSTALLED THEREIN. THE OCCUPANT LOAD FOR AREAS IN WHICH
 FIXED SEATING IS NOT INSTALLED, SUCH AS WAITING SPACES,
 SHALL BE DETERMINED IN ACCORDANCE WITH SECTION 1004.5
 AND ADDED TO THE NUMBER OF FIXED SEATS.
  