| 2021-08-24 14:30:32 | RESTAURANT BUILDOUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) DRAWING G200 SHOWS THE ASSEMBLY AREA AS HAVING AN | | | OCCUPANT LOAD OF 59 WHICH WILL REQUIRE 2 EXITS FROM | | | THAT AREA - YOU CANNOT EXIT THRU A KITCHEN PER FBC | | | 1016.2 (5) EGRESS SHALL NOT PASS THROUGH KITCHENS, | | | STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR | | | PURPOSES. | | | PLEASE RE CALCULATE THE ASSEMBLY AREA - FBC 1004.6 | | | FIXED SEATING. | | | FOR AREAS HAVING FIXED SEATS AND AISLES, THE OCCUPANT | | | LOAD SHALL BE DETERMINED BY THE NUMBER OF FIXED SEATS | | | INSTALLED THEREIN. THE OCCUPANT LOAD FOR AREAS IN WHICH | | | FIXED SEATING IS NOT INSTALLED, SUCH AS WAITING SPACES, | | | SHALL BE DETERMINED IN ACCORDANCE WITH SECTION 1004.5 | | | AND ADDED TO THE NUMBER OF FIXED SEATS. | | | |
|