| 2021-07-09 10:18:51 | 07/09/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET G-100; |
| | A. UNDER TOILET AND PLUMBING FACILITIES, IT SHOWS THE |
| | GRAB BARS IN A VERTICAL POSITION. GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION PER THE 2020 FBC ACC |
| | SEC. 609.4. |
| | |
| | B. IN THE SAME DETAIL UNDER TOILET TISSUE DISPENSER |
| | LOCATION HAS A 12 INCHES MAX. THE TOILET PAPER |
| | DISPENSERS SHALL BE 7-INCHES MINIMUM AND 9-INCHES |
| | MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE |
| | CENTERLINE OF THE DISPENSER PER THE 2020 FBC ACC SEC. |
| | 604.7. |
| | |
| | C. IN THE SAME DETAIL UNDER CLEARANCE REQUIREMENTS AT |
| | THE LAVATORY, THE 40-INCHES MAX SHALL BE TO THE |
| | REFLECTIVE PART OF THE MIRROR NEEDS TO BE THE OF |
| | 40-INCHES TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC |
| | SEC. 603.3. |
| | |
| | 2. ON SHEET A-130, IT SHOWS THE WRONG CLEAR FLOOR SPACE |
| | FOR THE TOILETS. THE CLEAR FLOOR SPACE SHALL BE |
| | 60-INCHES MINIMUM MEASURED PERPENDICULAR FROM THE |
| | SIDEWALL, AND 56-INCHES MINIMUM MEASURED PERPENDICULAR |
| | FROM THE REAR WALL PER THE 2020 FBC ACC. SEC. 604.3.1. |
| | |
| | 3. ON SHEET A- 131 UNDER EQUIPMENT SCHEDULE "K"; |
| | A. UNDER THE ICEMAKER SHALL BE EQUIPPED WITH AN IN-LINE |
| | VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER THE |
| | 2020 FBC SEC. 608.13.10. WOULD YOU PLEASE MAKE A NOTE |
| | ON THE REMARKS? |
| | |
| | B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. WOULD YOU PLEASE MAKE A NOTE ON THE REMARKS? |
| | |
| | 4. ON SHEET A-200 ON DETAIL 1 FOR ENLARGED RESTROOM |
| | PLAN; |
| | A. REMOVE THE 30-INCHES BY 48-INCHES SPACE IN FRONT OF |
| | THE WATER CLOSET AS IT IS NOT REQUIRED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. THE DOORS ARE IN THE CLEAR FLOOR SPACE OF THE LAVS. |
| | PLEASE SHOW THE TURNING SPACE DIAMETER- SPACE SHALL BE |
| | A SPACE OF 60 INCHES DIAMETER MINIMUM PER THE 2020 FBC |
| | ACC SEC. 304.3. |
| | |
| | C. PLEASE ONLY SHOW ONE CLEAR FLOOR SPACE IN FRONT OF |
| | LAVS, AS THERE ARE THREE DIFFERENT HATCH MARKS, FOR |
| | CLARITY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. THE REAR GRAB BAR SAYS 11-INCHES TO CENTER. WOULD |
| | YOU PLEASE CORRECT IT TO 12-INCHES PER THE 2020 ACC |
| | SEC. 604.5.2 REAR WALL? |
| | |
| | E. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER |
| | 2020 FBC P 425.3 WATER CLOSET SEATS |
| | |
| | 5. ON SHEET A-200 ON DETAIL 2, 5, 8, AND 9 ALL RR |
| | ELEVATION; |
| | A. THE BOTTOM ON THE LAV SHALL BE A MINIMUM OF |
| | 27-INCHES KNEE CLEARANCE PER THE 2020 FBC SEC. 306.3. |
| | |
| | B. THE MIRROR'S REFLECTIVE PART NEEDS TO BE 40-INCHES |
| | TO THE REFLECTIVE SIDE PER THE 2017 FBC ACC SEC. 603.3. |
| | |
| | 6. ON SHEET A-200 ON DETAIL 3, 6, AND 9, ALL RR |
| | ELEVATION ON ANY OF THE DETAILS SHOW THE TOILET SEATS |
| | NEED TO BE 17-INCHES TO 19-INCHES MAXIMUM MEASURED TO |
| | THE TOP OF THE SEAT PER THE 2020 FBC ACC SEC. 604.4 |
| | SEATS. |
| | |
| | 7. ON SHEET A-300, PLEASE PROVIDE DETAIL ON HOW GRAB |
| | BARS REINFORCEMENT IN WALLS. WOULD YOU PLEASE SHOW THE |
| | MINIMUM AND MAXIMUM DISTANCE FROM FLOOR PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 8. ON SHEET P-100, UNDER GENERAL NOTES #17, IT REFERS |
| | TO THE 2017 FBC 6TH EDITION. WOULD YOU PLEASE CORRECT |
| | TO CURRENT EDITION PER THE WPB AMENDMENTS TO FBC 102.3 |
| | APPLICATION OF REFERENCES? |
| | |
| | 9. ON SHEET P-101 UNDER SCOPE OF WORK #A, IT REFERS TO |
| | THE 2017 FBC 6TH EDITION. WOULD YOU PLEASE CORRECT TO |
| | CURRENT EDITION PER THE WPB AMENDMENTS TO FBC 102.3 |
| | APPLICATION OF REFERENCES? |
| | |
| | 10. ON SHEET P-101 AND G-300, IT REFERS TO GAS AND NOT |
| | ISOMETRIC GAS SIZING, TABLES AND APPLIANCE MANUFACTURE |
| | SPECIFICATION WAS SUPPLIED. YOU MAY CHOOSE TO HAVE A |
| | GAS REVIEW DONE THIS TIME AND ADDRESS THE COMMENTS |
| | ABOVE. THIS WILL HAVE THE GAS APPROVE FOR A SUB PERMIT, |
| | OR IF YOU DECIDED NOT TO ADDRESS THESE COMMENTS, PLEASE |
| | PUT A NOTE ON THE PLANS ( A SEPARATE PERMIT BY A |
| | LICENSED CONTRACTOR FOR THE GAS SYSTEM). AN N WILL BE |
| | PLACED ON THIS REVIEW, WHICH STANDS FOR NOT REQUIRED |
| | BUT, A SUB PERMIT WON'T BE ISSUED UNIT A REVIEW IS DONE |
| | FOR THAT SUB PERMIT, SO PLEASE BE ADVISED ON THIS |
| | PROCEDURE. |
| | |
| | 11. ON SHEET P-301, IT SHOWS A BOTTLE FILLER. DOES IT |
| | REQUIRE TO BE UNDER THE ACCESSIBILITY CODE AND HAVE A |
| | HIGH AND LOW WITH CLEAR FLOOR SPACE? WOULD YOU PLEASE |
| | CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 12. ON SHEET P-302, UNDER REFERENCE NOTE #4, THE |
| | ICEMAKER SHALL BE EQUIPPED WITH AN IN-LINE VACUUM |
| | BREAKER THAT COMPLIES WITH ASSE 1024 PER THE 2020 FBC |
| | SEC. 608.13.10. |
| | |
| | 13. ON SHEET P-500; |
| | A. SIZES ARE MISSING ON VERTICAL AND HORIZONTAL PIPES; |
| | TOO MANY TO MENTION. WOULD YOU PLEASE CORRECT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. THE BOTTLE FILLER, ICEMAKER, WATER HEATER DRAIN, AND |
| | LAVS ARE NOT ALLOWED TO GO INTO THE GREASE INTERCEPTOR. |
| | PLEASE REFER TO 64E-6, FLORIDA ADMINISTRATIVE CODE FOR |
| | PROPER DISPLACEMENT TO THE SANITARY OR GREASE |
| | INTERCEPTOR PER THE 64E-6. STANDARDS FOR ONSITE SEWAGE |
| | TREATMENT AND DISPOSAL SYSTEMS. |
| | |
| | 14. ON SHEET P-501; |
| | A. PLEASE PROVIDE A SHUTOFF VALVE ON BOTH SIDES OF THE |
| | RECIRCULATING PUMP PER THE 2020 FBC SEC. P 606.2 #3. |
| | ALSO, SHOW ON HEATER DETAIL P-700 #11. |
| | |
| | B. PLEASE PROVIDE A HAMMER ARRESTOR ON BOTTLE FILLER |
| | AND ANY OTHER QUICK CLOSING VALVE PER THE 2020 FBC SEC. |
| | 604.9. |
| | |
| | C. PLEASE SHOW THE ATMOSPHERIC-TYPE VACUUM BREAKERS ON |
| | THE BOTTOM FEED HEATER TANK PER THE 2020 FBC SEC. |
| | 608.14.6. |
| | |
| | D. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES |
| | MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE |
| | REFER TO THE 2020 FBC ENERGY CODE TABLE C404.5.1. |
| | |
| | 15. ON SHEET P-600 UNDER EQUIPMENT SCHEDULE; |
| | A. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN |
| | IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER |
| | THE 2020 FBC SEC. 608.13.10. WOULD YOU PLEASE MAKE A |
| | NOTE ON THE REMARKS? |
| | |
| | B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. WOULD YOU PLEASE MAKE A NOTE ON REMARKS? |
| | |
| | 16. ON SHEET P-700 |
| | A. PLEASE PROVIDE DETAILS 1, 5, AND 8 FOR THE UL USE |
| | FOR THE SYSTEM AND THE FIRE-RATED ASSEMBLY PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | B. PLEASE PROVIDE DETAIL FOR THE MULTIPLE-COMPARTMENT |
| | SINK SHOWING THE DISCHARGE INDEPENDENTLY TO A WASTE |
| | RECEPTOR PER THE 2020 FBC P 802.1.1. |
| | |
| | WOULD YOU PLEASE PLACE A NOTE ON A PLAN THAT THE GREASE |
| | INTERCEPTOR IS UNDER A DIFFERENT PERMIT WITH SIZING |
| | CALCULATION? |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |