Plan Review Notes
Plan Review Notes For Permit 21060874
Permit Number 21060874
Review Stop P
Sequence Number 1
Notes
Date Text
2021-07-09 10:18:5107/09/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET G-100;
 A. UNDER TOILET AND PLUMBING FACILITIES, IT SHOWS THE
 GRAB BARS IN A VERTICAL POSITION. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION PER THE 2020 FBC ACC
 SEC. 609.4.
  
 B. IN THE SAME DETAIL UNDER TOILET TISSUE DISPENSER
 LOCATION HAS A 12 INCHES MAX. THE TOILET PAPER
 DISPENSERS SHALL BE 7-INCHES MINIMUM AND 9-INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER PER THE 2020 FBC ACC SEC.
 604.7.
  
 C. IN THE SAME DETAIL UNDER CLEARANCE REQUIREMENTS AT
 THE LAVATORY, THE 40-INCHES MAX SHALL BE TO THE
 REFLECTIVE PART OF THE MIRROR NEEDS TO BE THE OF
 40-INCHES TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC
 SEC. 603.3.
  
 2. ON SHEET A-130, IT SHOWS THE WRONG CLEAR FLOOR SPACE
 FOR THE TOILETS. THE CLEAR FLOOR SPACE SHALL BE
 60-INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDEWALL, AND 56-INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL PER THE 2020 FBC ACC. SEC. 604.3.1.
  
 3. ON SHEET A- 131 UNDER EQUIPMENT SCHEDULE "K";
 A. UNDER THE ICEMAKER SHALL BE EQUIPPED WITH AN IN-LINE
 VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER THE
 2020 FBC SEC. 608.13.10. WOULD YOU PLEASE MAKE A NOTE
 ON THE REMARKS?
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THE REMARKS?
  
 4. ON SHEET A-200 ON DETAIL 1 FOR ENLARGED RESTROOM
 PLAN;
 A. REMOVE THE 30-INCHES BY 48-INCHES SPACE IN FRONT OF
 THE WATER CLOSET AS IT IS NOT REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. THE DOORS ARE IN THE CLEAR FLOOR SPACE OF THE LAVS.
 PLEASE SHOW THE TURNING SPACE DIAMETER- SPACE SHALL BE
 A SPACE OF 60 INCHES DIAMETER MINIMUM PER THE 2020 FBC
 ACC SEC. 304.3.
  
 C. PLEASE ONLY SHOW ONE CLEAR FLOOR SPACE IN FRONT OF
 LAVS, AS THERE ARE THREE DIFFERENT HATCH MARKS, FOR
 CLARITY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THE REAR GRAB BAR SAYS 11-INCHES TO CENTER. WOULD
 YOU PLEASE CORRECT IT TO 12-INCHES PER THE 2020 ACC
 SEC. 604.5.2 REAR WALL?
  
 E. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS
  
 5. ON SHEET A-200 ON DETAIL 2, 5, 8, AND 9 ALL RR
 ELEVATION;
 A. THE BOTTOM ON THE LAV SHALL BE A MINIMUM OF
 27-INCHES KNEE CLEARANCE PER THE 2020 FBC SEC. 306.3.
  
 B. THE MIRROR'S REFLECTIVE PART NEEDS TO BE 40-INCHES
 TO THE REFLECTIVE SIDE PER THE 2017 FBC ACC SEC. 603.3.
  
 6. ON SHEET A-200 ON DETAIL 3, 6, AND 9, ALL RR
 ELEVATION ON ANY OF THE DETAILS SHOW THE TOILET SEATS
 NEED TO BE 17-INCHES TO 19-INCHES MAXIMUM MEASURED TO
 THE TOP OF THE SEAT PER THE 2020 FBC ACC SEC. 604.4
 SEATS.
  
 7. ON SHEET A-300, PLEASE PROVIDE DETAIL ON HOW GRAB
 BARS REINFORCEMENT IN WALLS. WOULD YOU PLEASE SHOW THE
 MINIMUM AND MAXIMUM DISTANCE FROM FLOOR PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 8. ON SHEET P-100, UNDER GENERAL NOTES #17, IT REFERS
 TO THE 2017 FBC 6TH EDITION. WOULD YOU PLEASE CORRECT
 TO CURRENT EDITION PER THE WPB AMENDMENTS TO FBC 102.3
 APPLICATION OF REFERENCES?
  
 9. ON SHEET P-101 UNDER SCOPE OF WORK #A, IT REFERS TO
 THE 2017 FBC 6TH EDITION. WOULD YOU PLEASE CORRECT TO
 CURRENT EDITION PER THE WPB AMENDMENTS TO FBC 102.3
 APPLICATION OF REFERENCES?
  
 10. ON SHEET P-101 AND G-300, IT REFERS TO GAS AND NOT
 ISOMETRIC GAS SIZING, TABLES AND APPLIANCE MANUFACTURE
 SPECIFICATION WAS SUPPLIED. YOU MAY CHOOSE TO HAVE A
 GAS REVIEW DONE THIS TIME AND ADDRESS THE COMMENTS
 ABOVE. THIS WILL HAVE THE GAS APPROVE FOR A SUB PERMIT,
 OR IF YOU DECIDED NOT TO ADDRESS THESE COMMENTS, PLEASE
 PUT A NOTE ON THE PLANS ( A SEPARATE PERMIT BY A
 LICENSED CONTRACTOR FOR THE GAS SYSTEM). AN N WILL BE
 PLACED ON THIS REVIEW, WHICH STANDS FOR NOT REQUIRED
 BUT, A SUB PERMIT WON'T BE ISSUED UNIT A REVIEW IS DONE
 FOR THAT SUB PERMIT, SO PLEASE BE ADVISED ON THIS
 PROCEDURE.
  
 11. ON SHEET P-301, IT SHOWS A BOTTLE FILLER. DOES IT
 REQUIRE TO BE UNDER THE ACCESSIBILITY CODE AND HAVE A
 HIGH AND LOW WITH CLEAR FLOOR SPACE? WOULD YOU PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 12. ON SHEET P-302, UNDER REFERENCE NOTE #4, THE
 ICEMAKER SHALL BE EQUIPPED WITH AN IN-LINE VACUUM
 BREAKER THAT COMPLIES WITH ASSE 1024 PER THE 2020 FBC
 SEC. 608.13.10.
  
 13. ON SHEET P-500;
 A. SIZES ARE MISSING ON VERTICAL AND HORIZONTAL PIPES;
 TOO MANY TO MENTION. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. THE BOTTLE FILLER, ICEMAKER, WATER HEATER DRAIN, AND
 LAVS ARE NOT ALLOWED TO GO INTO THE GREASE INTERCEPTOR.
 PLEASE REFER TO 64E-6, FLORIDA ADMINISTRATIVE CODE FOR
 PROPER DISPLACEMENT TO THE SANITARY OR GREASE
 INTERCEPTOR PER THE 64E-6. STANDARDS FOR ONSITE SEWAGE
 TREATMENT AND DISPOSAL SYSTEMS.
  
 14. ON SHEET P-501;
 A. PLEASE PROVIDE A SHUTOFF VALVE ON BOTH SIDES OF THE
 RECIRCULATING PUMP PER THE 2020 FBC SEC. P 606.2 #3.
 ALSO, SHOW ON HEATER DETAIL P-700 #11.
  
 B. PLEASE PROVIDE A HAMMER ARRESTOR ON BOTTLE FILLER
 AND ANY OTHER QUICK CLOSING VALVE PER THE 2020 FBC SEC.
 604.9.
  
 C. PLEASE SHOW THE ATMOSPHERIC-TYPE VACUUM BREAKERS ON
 THE BOTTOM FEED HEATER TANK PER THE 2020 FBC SEC.
 608.14.6.
  
 D. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES
 MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE
 REFER TO THE 2020 FBC ENERGY CODE TABLE C404.5.1.
  
 15. ON SHEET P-600 UNDER EQUIPMENT SCHEDULE;
 A. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2020 FBC SEC. 608.13.10. WOULD YOU PLEASE MAKE A
 NOTE ON THE REMARKS?
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON REMARKS?
  
 16. ON SHEET P-700
 A. PLEASE PROVIDE DETAILS 1, 5, AND 8 FOR THE UL USE
 FOR THE SYSTEM AND THE FIRE-RATED ASSEMBLY PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 B. PLEASE PROVIDE DETAIL FOR THE MULTIPLE-COMPARTMENT
 SINK SHOWING THE DISCHARGE INDEPENDENTLY TO A WASTE
 RECEPTOR PER THE 2020 FBC P 802.1.1.
  
 WOULD YOU PLEASE PLACE A NOTE ON A PLAN THAT THE GREASE
 INTERCEPTOR IS UNDER A DIFFERENT PERMIT WITH SIZING
 CALCULATION?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  