Plan Review Notes
Plan Review Notes For Permit 21060874
Permit Number 21060874
Review Stop B
Sequence Number 1
Notes
Date Text
2021-07-16 10:18:55RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWING G-100 - TOILET PAPER DISPENSER INSTALLATION
 DIMENSIONS ARE INCORRECT FBC A604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS.
 2) ACCESSIBLE RESTROOM MIRRORS SHOULD INDICATE THAT THE
 MAXIMUM HEIGHT IS TO THE "REFLECTIVE SURFACE" PER FBC
 A603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 3) DRAWING A-200 - ENLARGED RESTROOM PLAN - THE
 DIMENSIONS FOR THE TOILET REAR GRAB BAR ARE INCORRECT
 FBC A604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 4) DRAWING A-300 - SLAB REPAIR SECTIONS SHOULD SHOW IF
 TERMITE TREATMENT IS REQUIRED FBC 1816.1.2
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, SOIL AREA DISTURBED AFTER INITIAL CHEMICAL
 SOIL TREATMENT SHALL BE RETREATED WITH A CHEMICAL SOIL
 TREATMENT, INCLUDING SPACES BOXED OR FORMED.
  