| 2021-06-23 08:19:39 | PLAN REVIEW / SIGNATURES |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NEC2017 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | RE: 1) GENERATOR ANCHOR ATTACHMENT DETAIL |
| | 2) GENERATOR PAD STRUCTURAL PAGE S9 |
| | 3) REVISED PLAN PAGE E4 REQUIRES SIGNATURE AND SEAL OF |
| | DOR. SEE ELECTRICAL REVIEW COMMENTS UNDER RES REV |
| | 21061149 (AS-BUILTS) |
| | |
| | NOTICE: PLAN PAGE S9 IS NOT REQUIRED FOR THIS |
| | SUBMITTAL. GENERATOR LOCATION IS SHOWN ON SITE PLAN AND |
| | STRUCTURAL PAD DETAILS ARE PROVIDED ON ANCHOR DETAIL. |
| | YOU MAY REMOVE THIS PAGE. |
| | |
| | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND |
| | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, |
| | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR |
| | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL |
| | SIGNATURE. |
| | |
| | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR |
| | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL |
| | WET SEAL AND SIGNATURE TO: |
| | |
| | BUILDING DIVISION, FIRST FLOOR |
| | CITY OF WEST PALM BEACH |
| | 401 CLEMATIS ST |
| | WEST PALM BEACH, FL 33401 |
| | |
| | |