Plan Review Notes
Plan Review Notes For Permit 21060844
Permit Number 21060844
Review Stop P
Sequence Number 5
Notes
Date Text
2022-10-03 13:10:515TH REVIEW FBC-2017 PLUMBING
 PERMIT- 21060844
 10/3/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE PLANS WERE NOT
 CORRECTED ACCORDING TO PREVIOIUS COMMENTS #6, 10, & 11
 BELOW. PLEASE NOTE NO BACKFLOW PERMIT APPLICATIONS HAVE
 NOT BEEN SUBMITTED FOR POTABLE WATER SERVICES,
 FIRELINES, COOLING TOWERS, BOILERS, AND IRRIGATION AND
 POOL RECIRCULATION SYSTEMS SUPPLIED BY POTABLE WATER
 LINES- SECS. C, D, & E WPB UTILITES CROSS CONNECTION
 MANUAL, AND SEC. 608.3 FBC P.
 THE CITY OF WPB BUILDING DEPT. REQUIRES THAT PERMIT
 APPLICATIONS FOR POTABLE WATER BACKFLOW PREVENTERS AND
 GREASE INTERCEPTORS ARE REQUIRED TO BE SUBMITTED PRIOR
 TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 6) FAILED. P4.05N: AN RPZ BACKFLOW PREVENTER DEVICE IS
 REQUIRED FOR THE WATER SUPPLY TO THE COOLING TOWERS-
 SEC. 608.3 FBC P AND SEC E, TABLE 1.1 WPB UTILITIES
 CROSS-CONNECTION MANUAL. PLEASE NOTE A SEPARATE PERMIT
 IS REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE NOTES ON
 THE DRAWINGS TO INDICATE COMPLIANCE. NOT PROVIDED.
  
 10) FAILED. P5.05S: RPZ BACKFLOW PREVENTER DEVICES ARE
 REQUIRED AT EACH WATER SUPPLY PIPE TO THE COOLING
 TOWERS- SECS. 608.3 FBC P AND SEC E, TABLE 1.1 WPB
 UTILITIES CROSS-CONNECTION MANUAL. PLEASE NOTE SEPARATE
 PERMITS ARE REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE
 NOTES ON THE DRAWINGS TO INDICATE COMPLIANCE. NOT
 PROVIDED.
  
 11) FAILED. P5.05S: PROVIDE ASSE 1012 OR CSA B64.3
 APPROVED BACKFLOW PREVENTERS WITH INTERMEDIATE
 ATMOSPHERIC VENTS TO THE BOILERS- SEC. 608.1.7.2 FBC P.
 NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  