| Date |
Text |
| 2022-10-03 13:10:51 | 5TH REVIEW FBC-2017 PLUMBING |
| | PERMIT- 21060844 |
| | 10/3/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. THE PLANS WERE NOT |
| | CORRECTED ACCORDING TO PREVIOIUS COMMENTS #6, 10, & 11 |
| | BELOW. PLEASE NOTE NO BACKFLOW PERMIT APPLICATIONS HAVE |
| | NOT BEEN SUBMITTED FOR POTABLE WATER SERVICES, |
| | FIRELINES, COOLING TOWERS, BOILERS, AND IRRIGATION AND |
| | POOL RECIRCULATION SYSTEMS SUPPLIED BY POTABLE WATER |
| | LINES- SECS. C, D, & E WPB UTILITES CROSS CONNECTION |
| | MANUAL, AND SEC. 608.3 FBC P. |
| | THE CITY OF WPB BUILDING DEPT. REQUIRES THAT PERMIT |
| | APPLICATIONS FOR POTABLE WATER BACKFLOW PREVENTERS AND |
| | GREASE INTERCEPTORS ARE REQUIRED TO BE SUBMITTED PRIOR |
| | TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT AN |
| | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 6) FAILED. P4.05N: AN RPZ BACKFLOW PREVENTER DEVICE IS |
| | REQUIRED FOR THE WATER SUPPLY TO THE COOLING TOWERS- |
| | SEC. 608.3 FBC P AND SEC E, TABLE 1.1 WPB UTILITIES |
| | CROSS-CONNECTION MANUAL. PLEASE NOTE A SEPARATE PERMIT |
| | IS REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE NOTES ON |
| | THE DRAWINGS TO INDICATE COMPLIANCE. NOT PROVIDED. |
| | |
| | 10) FAILED. P5.05S: RPZ BACKFLOW PREVENTER DEVICES ARE |
| | REQUIRED AT EACH WATER SUPPLY PIPE TO THE COOLING |
| | TOWERS- SECS. 608.3 FBC P AND SEC E, TABLE 1.1 WPB |
| | UTILITIES CROSS-CONNECTION MANUAL. PLEASE NOTE SEPARATE |
| | PERMITS ARE REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE |
| | NOTES ON THE DRAWINGS TO INDICATE COMPLIANCE. NOT |
| | PROVIDED. |
| | |
| | 11) FAILED. P5.05S: PROVIDE ASSE 1012 OR CSA B64.3 |
| | APPROVED BACKFLOW PREVENTERS WITH INTERMEDIATE |
| | ATMOSPHERIC VENTS TO THE BOILERS- SEC. 608.1.7.2 FBC P. |
| | NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |