Plan Review Notes
Plan Review Notes For Permit 21060844
Permit Number 21060844
Review Stop P
Sequence Number 4
Notes
Date Text
2022-07-21 14:56:402ND REVIEW FBC-2017 PLUMBING
 PERMIT- 21060844
 7/21/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED
 BELOW WITH ADDITIONAL NOTES IN CAPS. THE SUBMITTED
 NARRATIVE DID NOT APPEAR TO ADDRESS ALL OF THE
 COMMENTS. PLEASE CONTACT ME IF YOU HAVE QUESTIONS.
  
 1) FAILED. REVISE SHEETS A1.201N & A1.201S TO MATCH THE
 REVISED PLUMBING AND GAS PLANS SHOWING THE NEW OUTDOOR
 KITCHEN AND THE MULTI-PURPOSE FIXTURES AND APPLIANCES-
 SEC. 107.2.1 WPB. THE ARCHITECT REVISED THE PLANS BUT
 DID NOT ADD THE OUTDOOR KITCHEN ON THE DRAWINGS AS
 REQUESTED.
  
 3) FAILED. SHEETS P2.01N & P2.01S: PROVIDE CANOPY
 DRAINAGE DETAILS- DRAIN LOCATIONS, DRAIN PIPE RUNS AND
 DISCHARGE LOCATIONS- SEC. 1101.2 FBC P. NOT PROVIDED.
  
 4) FAILED. P4.05N: SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION GUIDELINES FOR THE EYE WASH STATION-
 SECS. 411.2 FBC P. THE STATION SHALL MEET THE IZ358.1
 STANDARD. PROVIDE DETAILS ON THE PLAN SHOWING
 COMPLIANCE WITH THE GUIDELINE. PLEASE NOTE THAT TEPID
 WATER- TEMPERATURE BETWEEN 60 DEGREES F AND 100 DEGREES
 F- SHALL BE DELIVERED FROM THE STATION PER THE
 STANDARD. NOT PROVIDED.
  
 5) FAILED. P4.05N: SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION GUIDELINES FOR THE STEAM GENERATOR-
 SEC. 502.1 FBC P. A) PROVIDE A WATER HAMMER ARRESTOR
 FOR THE SUPPLY LINE, AND INDICATE THE TYPE OF BACKFLOW
 PREVENTER TO BE INSTALLED- SECS. 604.9 & 608.3 FBC P.
 NOT PROVIDED.
  
 6) FAILED. P4.05N: AN RPZ BACKFLOW PREVENTER DEVICE IS
 REQUIRED FOR THE WATER SUPPLY TO THE COOLING TOWERS-
 SEC. 608.3 FBC P AND SEC E, TABLE 1.1 WPB UTILITIES
 CROSS-CONNECTION MANUAL. PLEASE NOTE A SEPARATE PERMIT
 IS REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE NOTES ON
 THE DRAWINGS TO INDICATE COMPLIANCE. NOT PROVIDED.
  
 10) FAILED. P5.05S: RPZ BACKFLOW PREVENTER DEVICES ARE
 REQUIRED AT EACH WATER SUPPLY PIPE TO THE COOLING
 TOWERS- SECS. 608.3 FBC P AND SEC E, TABLE 1.1 WPB
 UTILITIES CROSS-CONNECTION MANUAL. PLEASE NOTE SEPARATE
 PERMITS ARE REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE
 NOTES ON THE DRAWINGS TO INDICATE COMPLIANCE. NOT
 PROVIDED.
  
 11) FAILED. P5.05S: PROVIDE ASSE 1012 OR CSA B64.3
 APPROVED BACKFLOW PREVENTERS WITH INTERMEDIATE
 ATMOSPHERIC VENTS TO THE BOILERS- SEC. 608.1.7.2 FBC P.
 NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  