| 2022-07-21 14:56:40 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 21060844 |
| | 7/21/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED |
| | BELOW WITH ADDITIONAL NOTES IN CAPS. THE SUBMITTED |
| | NARRATIVE DID NOT APPEAR TO ADDRESS ALL OF THE |
| | COMMENTS. PLEASE CONTACT ME IF YOU HAVE QUESTIONS. |
| | |
| | 1) FAILED. REVISE SHEETS A1.201N & A1.201S TO MATCH THE |
| | REVISED PLUMBING AND GAS PLANS SHOWING THE NEW OUTDOOR |
| | KITCHEN AND THE MULTI-PURPOSE FIXTURES AND APPLIANCES- |
| | SEC. 107.2.1 WPB. THE ARCHITECT REVISED THE PLANS BUT |
| | DID NOT ADD THE OUTDOOR KITCHEN ON THE DRAWINGS AS |
| | REQUESTED. |
| | |
| | 3) FAILED. SHEETS P2.01N & P2.01S: PROVIDE CANOPY |
| | DRAINAGE DETAILS- DRAIN LOCATIONS, DRAIN PIPE RUNS AND |
| | DISCHARGE LOCATIONS- SEC. 1101.2 FBC P. NOT PROVIDED. |
| | |
| | 4) FAILED. P4.05N: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND INSTALLATION GUIDELINES FOR THE EYE WASH STATION- |
| | SECS. 411.2 FBC P. THE STATION SHALL MEET THE IZ358.1 |
| | STANDARD. PROVIDE DETAILS ON THE PLAN SHOWING |
| | COMPLIANCE WITH THE GUIDELINE. PLEASE NOTE THAT TEPID |
| | WATER- TEMPERATURE BETWEEN 60 DEGREES F AND 100 DEGREES |
| | F- SHALL BE DELIVERED FROM THE STATION PER THE |
| | STANDARD. NOT PROVIDED. |
| | |
| | 5) FAILED. P4.05N: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND INSTALLATION GUIDELINES FOR THE STEAM GENERATOR- |
| | SEC. 502.1 FBC P. A) PROVIDE A WATER HAMMER ARRESTOR |
| | FOR THE SUPPLY LINE, AND INDICATE THE TYPE OF BACKFLOW |
| | PREVENTER TO BE INSTALLED- SECS. 604.9 & 608.3 FBC P. |
| | NOT PROVIDED. |
| | |
| | 6) FAILED. P4.05N: AN RPZ BACKFLOW PREVENTER DEVICE IS |
| | REQUIRED FOR THE WATER SUPPLY TO THE COOLING TOWERS- |
| | SEC. 608.3 FBC P AND SEC E, TABLE 1.1 WPB UTILITIES |
| | CROSS-CONNECTION MANUAL. PLEASE NOTE A SEPARATE PERMIT |
| | IS REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE NOTES ON |
| | THE DRAWINGS TO INDICATE COMPLIANCE. NOT PROVIDED. |
| | |
| | 10) FAILED. P5.05S: RPZ BACKFLOW PREVENTER DEVICES ARE |
| | REQUIRED AT EACH WATER SUPPLY PIPE TO THE COOLING |
| | TOWERS- SECS. 608.3 FBC P AND SEC E, TABLE 1.1 WPB |
| | UTILITIES CROSS-CONNECTION MANUAL. PLEASE NOTE SEPARATE |
| | PERMITS ARE REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE |
| | NOTES ON THE DRAWINGS TO INDICATE COMPLIANCE. NOT |
| | PROVIDED. |
| | |
| | 11) FAILED. P5.05S: PROVIDE ASSE 1012 OR CSA B64.3 |
| | APPROVED BACKFLOW PREVENTERS WITH INTERMEDIATE |
| | ATMOSPHERIC VENTS TO THE BOILERS- SEC. 608.1.7.2 FBC P. |
| | NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |