| 2022-07-21 15:32:08 | 2ND REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 21060844 |
| | 7/21//22 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITION NOTES FOR |
| | CLARIFICATION. PLEASE CONTACT ME IF YOU HAVE QUESTIONS. |
| | |
| | 1) FAILED A & B. SHEET P4.11N NOTE CORRECTIONS- SEC. |
| | 107.2.1 WPB: A) NOTE #8 IS INDICATED TO BE OMITTED BUT |
| | IT IS SHOWN ON THE RISER. B) NOTE #10 SHOWS INCORRECT |
| | TOTAL GAS LOAD FOR THE SYSTEM. NO CORRECTIONS PROVIDED. |
| | |
| | 2) FAILED. P4.11N REGULATORS- SEC. 410.1- 410.3: A) |
| | LABEL ALL LOW-PRESSURE REGULATOR LOCATIONS. B) PROVIDE |
| | VENTING DETAILS IF APPLICABLE- VENT PIPING MATERIAL, |
| | PIPING RUNS AND DISCHARGE LOCATIONS. C) SUBMIT |
| | MANUFACTURER?S SPECIFICATIONS MARKED UP TO SHOW MODEL |
| | SELECTION AND INPUT AND OUTPUT. PIPE SIZES AND |
| | PRESSURES. LOW PRESSURE REGULATORS REQUIRED AT POOL |
| | HEATERS AND BBQ?S NOT LABELED. SPECS CAN BE DEFERRED |
| | SUBMITTALS. |
| | |
| | 3) FAILED. P4.11N: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND INSTALLATION INSTRUCTIONS FOR THE BBQ GRILLS AND |
| | THE FIREPIT- SECS. 623.1 & 636.1 FBC FG. A) PROVIDE BBQ |
| | GRILL ELEVATION VIEWS BASED ON THE INSTALL GUIDELINES |
| | SHOWING CLEARANCES TO COMBUSTIBLES AND THE OVERHEAD |
| | CANOPY. PLEASE NOTE THAT EXHAUST HOODS MAY BE REQUIRED |
| | PER THE MANUFACTURER'S GUIDELINES- SECS. 305.1 & 305.8 |
| | B) PROVIDE EQUIPMENT ANCHORING DETAILS FOR ALL OUTDOOR |
| | APPLIANCES- 301.10. NOT PROVIDED. DRAWINGS ARE REQUIRED |
| | BUT ANCHORING AND SPECS CAN BE DEFERRED. |
| | |
| | 4) FAILED. P4.11N: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE SOLENOID VALVES AND GAS LEAK DETECTORS- SED. |
| | 305.1 FBC FG. CAN BE DEFERRED. |
| | |
| | 5) FAILED. P4.11N: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND INSTALLATION MANUAL FOR THE GASTITE PIPING- SEC. |
| | 404.2 FBC FG. CAN BE DEFERRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |