| 2022-04-29 18:58:43 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 21060844 |
| | 4/29/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REVISE SHEETS A1.201N & A1.201S TO MATCH THE REVISED |
| | PLUMBING AND GAS PLANS SHOWING THE NEW OUTDOOR KITCHEN |
| | AND THE MULTI-PURPOSE FIXTURES AND APPLIANCES- SEC. |
| | 107.2.1 WPB. |
| | |
| | 2) PROVIDE ENLARGED DRAWINGS FOR OUTDOOR KITCHEN AND |
| | MULTIPURPOSE KITCHEN SHOWING COMPLIANCE WITH THE FBC |
| | ACC. PLEASE INCLUDE: |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR SINKS- |
| | SEC. 606.2. |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR |
| | APPLIANCES- SEC. 804.6. |
| | C) HEIGHTS OF SINKS MEASURED FROM THE FINISHED FLOORS |
| | TO THE SINK RIM OR COUNTER- SEC. 606.2. |
| | D) REACH HEIGHTS FOR APPLIANCE CONTROLS- SEC. 308.1. |
| | |
| | 3) SHEETS P2.01N & P2.01S: PROVIDE CANOPY DRAINAGE |
| | DETAILS- DRAIN LOCATIONS, DRAIN PIPE RUNS AND DISCHARGE |
| | LOCATIONS- SEC. 1101.2 FBC P. |
| | |
| | 4) P4.05N: SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION GUIDELINES FOR THE EYE WASH STATION- SECS. |
| | 411.2 FBC P. THE STATION SHALL MEET THE IZ358.1 |
| | STANDARD. PROVIDE DETAILS ON THE PLAN SHOWING |
| | COMPLIANCE WITH THE GUIDELINE. PLEASE NOTE THAT TEPID |
| | WATER- TEMPERATURE BETWEEN 60 DEGREES F AND 100 DEGREES |
| | F- SHALL BE DELIVERED FROM THE STATION PER THE |
| | STANDARD. |
| | |
| | 5) P4.05N: SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION GUIDELINES FOR THE STEAM GENERATOR- SEC. |
| | 502.1 FBC P. A) PROVIDE A WATER HAMMER ARRESTOR FOR THE |
| | SUPPLY LINE, AND INDICATE THE TYPE OF BACKFLOW |
| | PREVENTER TO BE INSTALLED- SECS. 604.9 & 608.3 FBC P. |
| | |
| | 6) P4.05N: AN RPZ BACKFLOW PREVENTER DEVICE IS REQUIRED |
| | FOR THE WATER SUPPLY TO THE COOLING TOWERS- SEC. 608.3 |
| | FBC P AND SEC E, TABLE 1.1 WPB UTILITIES |
| | CROSS-CONNECTION MANUAL. PLEASE NOTE A SEPARATE PERMIT |
| | IS REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE NOTES ON |
| | THE DRAWINGS TO INDICATE COMPLIANCE. |
| | |
| | 7) P412N: THIS SHEET IS CALLED OUT IN THE NARRATIVE BUT |
| | WAS NOT UPLOADED FOR REVIEW- SEC. 107.2.1 WPB. |
| | |
| | 8) P5.01S: THE RISER INDICATES WASTE WATER FROM THE |
| | POOL EQUIPMENT ROOM DISCHARGING TO THE SANITARY SYSTEM. |
| | PLEASE NOTE THAT SWIMMING POOL WASTEWATER IS PROHIBITED |
| | FROM DRAINING INTO THE SANITARY SYSTEM- SEC. 90-126(5). |
| | SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY |
| | SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES |
| | DEPARTMENT. |
| | SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| | STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| | ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| | BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW |
| | AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| | WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| | A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| | TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| | INLET). |
| | B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| | INLET TO DISCHARGE EFFLUENT. |
| | C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| | ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS |
| | PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| | D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| | PROPERTY. |
| | E) FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT |
| | O&M SUPERINTENDENT STEPHON HARRIS AT [email protected] OR |
| | 561-822-2168. |
| | F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, |
| | PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| | SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| | 822-2062 OR [email protected]. |
| | |
| | SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| | STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| | ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| | BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW |
| | AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| | WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| | THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO |
| | KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| | INLET). |
| | NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| | INLET TO DISCHARGE EFFLUENT. |
| | WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED |
| | TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS |
| | PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| | DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| | PROPERTY. |
| | FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT O&M |
| | SUPERINTENDENT STEPHON HARRIS AT [email protected] OR |
| | 561-822-2168. |
| | FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| | CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| | SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| | 822-2062 OR [email protected]. |
| | |
| | 9) P5.01S: PROVIDE AN EQUIPMENT SCHEDULE FOR THE SUMP |
| | PUMP AND PIT, AND AN ENLARGED PIPING DETAIL- SEC. |
| | 712.2- 712.3.3.2 FBC P. |
| | |
| | 10) P5.05S: RPZ BACKFLOW PREVENTER DEVICES ARE REQUIRED |
| | AT EACH WATER SUPPLY PIPE TO THE COOLING TOWERS- SECS. |
| | 608.3 FBC P AND SEC E, TABLE 1.1 WPB UTILITIES |
| | CROSS-CONNECTION MANUAL. PLEASE NOTE SEPARATE PERMITS |
| | ARE REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE NOTES ON |
| | THE DRAWINGS TO INDICATE COMPLIANCE. |
| | |
| | 11) P5.05S: PROVIDE ASSE 1012 OR CSA B64.3 APPROVED |
| | BACKFLOW PREVENTERS WITH INTERMEDIATE ATMOSPHERIC VENTS |
| | TO THE BOILERS- SEC. 608.1.7.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |