Plan Review Notes
Plan Review Notes For Permit 21060844
Permit Number 21060844
Review Stop M
Sequence Number 3
Notes
Date Text
2022-02-02 09:17:173RD CYCLE REVIEW FBC-2020 MECHANICAL
 PERMIT-21060844
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS THE 3RD TIME FOR A COMMENT ON OUTDOOR AIR
 CALCULATIONS. PLEASE RESPOND.
  
 SHEET M3.02- UNIT A2: THE DRYER VENT FOR THIS DRYER
 INSTALLATION HAS A TOTAL OF 7 90 DEGREE TURNS IN THE
 DESIGN. PLEASE SHOW FROM THE MANUFACTURER THAT THIS
 DRYER WILL ALLOW THE EXHAUST SYSTEM TO HAVE THAT MANY
 90?S. SHEET M3.03- UNIT B4, UNIT C1, SHEET M3.01- UNIT
 A3 ALL HAVE SIMILAR ISSUES. FBC M 504.8.4.2
  
 2) SHEET M-4.02: PLEASE UNDERSTAND FBC M 403.3.1.1
 TELLS US WE MUST USE THE OCCUPANT DENSITY FOR EACH USE
 OF SPACE AND NOT THE ARCHITECTURAL OCCUPANCY COUNT.
 PLEASE REWORK THE OUTDOOR AIR CALCULATIONS TO REFLECT
 THIS. THERE ARE OCCUPANCIES IN THE COMMON AREAS THAT
 HAVE A LOW OCCUPANT COUNT WHICH IN TURN DOES NOT LINE
 UP WITH THE OCCUPANCY DENSITY OF THE TABLE 403.3.1.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  