| 2022-02-02 09:17:17 | 3RD CYCLE REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21060844 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS IS THE 3RD TIME FOR A COMMENT ON OUTDOOR AIR |
| | CALCULATIONS. PLEASE RESPOND. |
| | |
| | SHEET M3.02- UNIT A2: THE DRYER VENT FOR THIS DRYER |
| | INSTALLATION HAS A TOTAL OF 7 90 DEGREE TURNS IN THE |
| | DESIGN. PLEASE SHOW FROM THE MANUFACTURER THAT THIS |
| | DRYER WILL ALLOW THE EXHAUST SYSTEM TO HAVE THAT MANY |
| | 90?S. SHEET M3.03- UNIT B4, UNIT C1, SHEET M3.01- UNIT |
| | A3 ALL HAVE SIMILAR ISSUES. FBC M 504.8.4.2 |
| | |
| | 2) SHEET M-4.02: PLEASE UNDERSTAND FBC M 403.3.1.1 |
| | TELLS US WE MUST USE THE OCCUPANT DENSITY FOR EACH USE |
| | OF SPACE AND NOT THE ARCHITECTURAL OCCUPANCY COUNT. |
| | PLEASE REWORK THE OUTDOOR AIR CALCULATIONS TO REFLECT |
| | THIS. THERE ARE OCCUPANCIES IN THE COMMON AREAS THAT |
| | HAVE A LOW OCCUPANT COUNT WHICH IN TURN DOES NOT LINE |
| | UP WITH THE OCCUPANCY DENSITY OF THE TABLE 403.3.1.1. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |