| 2021-11-08 15:30:49 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21060844 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE TAKE ANOTHER LOOK AT YOUR OUTDOOR AIR |
| | CALCULATIONS AS SEVERAL SEEM TO BE LOW. THE TV VIEWING |
| | AREA COULD BE CONSIDERED A DAY ROOM, THE THEATRE COULD |
| | ALSO. THE MULTIPURPOSE ROOMS SEEM TO HAVE A LOW |
| | OCCUPANT COUNT. PLEASE USE THE OCCUPANT DENSITY COLUMN |
| | FOR EACH USE OF SPACE. ASHRAE 62.1-2013 TABLE 6.2.2.1 |
| | |
| | 2) COMMENT 2 OF PREVIOUS CYCLE REVIEW. - SHEET M2.01G: |
| | PLEASE PROVIDE MECHANICAL SIZING CALCULATIONS FOR THIS |
| | NEW HP-G1.6. THE RESPONSE LETTER SAID THE LOAD |
| | CALCULATION WAS ATTACHED BUT I DO NOT SEE IT. |
| | |
| | 3) CLOTHES DRYER EXHAUST IS COVERED IN FBC M 504 AND I |
| | WOULD NOT THINK TO LOOK AT THE A SHEETS FOR DRYER |
| | INFORMATION. PLEASE PROVIDE THE SHEET NUMBERS THAT THE |
| | DRYER INFORMATION IS LOCATED. |
| | |
| | 4) THE DRYER VENT TABLE LISTED ON SHEET M3.02 ONLY |
| | LISTS INFORMATION FOR UP TO 4- 90 DEGREE TURNS. PLEASE |
| | PROVIDE MANUFACTURER?S INSTALLATION INSTRUCTIONS FOR |
| | THE ADDITIONAL 90 DEGREE TURNS SHOWN ON YOUR DRAWINGS. |
| | FBC M 504.8.4.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |