| 2021-07-19 17:10:20 | 07/19/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET 2.01N; |
| | A. THE RESTROOM WAS MOVED, AND N-105 A LABEL IS NOT |
| | PRESENT. WOULD YOU PLEASE LABEL PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | B. THE SINK IN THE MULTI-PURPOSE ROOM IS NOT SHOWN, AND |
| | NEITHER ARE THE REFRIGERATOR AND ICE MACHINE. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. THE SINK LAYOUT, BBQ, AND SHOWER ARE NOT SHOWN, AND |
| | THE SANITARY IS STILL SHOWS. WHERE WERE THEY MOVE TO? |
| | WOULD YOU PLEASE SHOW THE NEW LOCATION AND LABEL PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. IT SHOWS TWO BBQ AND A SINK IN A DIFFERENT LOCATION. |
| | WOULD YOU PLEASE PROVIDE THE DRAINAGE AND GAS TO IT? IF |
| | THE BBQ IS ENCLOSED IN A ROOM, THEY MAY REQUIRE A HOOD |
| | SYSTEM. THAT WILL NEED TO BE DETERMINED AND NOTED ON |
| | PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | E. PUMP ROOM/ MECHANICAL ROOM, NOT LABELS AND WORD PUMP |
| | ROOM NOT TOO VISIBLE WOULD YOU PLEASE MOVE AND LABEL |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | F. THE STORM HAS 16,820 SF 874 GPM IN THE PREVIOUS |
| | VERSION; NOW, IT HAS 7,990 419 GPM, AND THERE ARE TWO |
| | 8? SD DELETED. IF SO, PLEASE CLARIFY HOW THIS WATER |
| | WILL BE CAUGHT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | G. IN THE RESIDENTIAL ACTIVE USE AREA, THERE ARE WALLS |
| | MISSING WALLS ALL THE WAY UP TO THE STAFF LOCKER. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 2. ON SHEET 2.01S; |
| | A. IN THE RESIDENTIAL ACTIVE USE AREA, THERE ARE WALLS |
| | MISSING WALLS. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. ON KEYNOTE 15 BY POOL EQUIPMENT SAYS IT IS A |
| | CONTINUATION OF P201N. THAT IS NOT AN APPARENT |
| | REFERENCE TO THAT NUMBER. WOULD YOU PLEASE CORRECT OR |
| | CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. IN THE TRASH ROOM AREA, PLEASE LABEL THE 4-INCH |
| | FLOOR DRAIN WITH A REMOVABLE BASKET PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | C. IT SHOWS TWO BBQ AND A SINK IN A DIFFERENT LOCATION. |
| | WOULD YOU PLEASE PROVIDE THE DRAINAGE AND GAS TO IT? IF |
| | THE BBQ IS ENCLOSED IN A ROOM, THEY MAY REQUIRE A HOOD |
| | SYSTEM. THIS WILL NEED TO BE DETERMINED AND NOTED ON |
| | PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. THE SINK IN THE MULTI-PURPOSE ROOM IS NOT SHOWN, AND |
| | NEITHER ARE THE REFRIGERATOR AND ICE MACHINE. THERE IS |
| | A WALL MISSING AS WELL. WOULD YOU PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? PLEASE MOVE THE LABEL FOR |
| | THE MULTI-PURPOSE ROOM OVER AS IT HAS THE WATER LINES |
| | OVER IT. |
| | |
| | E. NUMBER 25 ON STAIRWELL 4 HAS A STORM DRAIN IN A |
| | STAIRWELL. IF THIS IS A PRESSURIZED STAIRWELL, IT IS |
| | NOT ALLOWED UNLESS IT IS IN A CHASE. WOULD YOU PLEASE |
| | CLARIFY OR MOVE PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | F. PUMP ROOM WAS MOVED, AND THERE SEEMS TO BE ONE SIDE |
| | THAT DOES NOT HAVE THE INCHES REQUIRED IN CLEARANCE PER |
| | THE MANUFACTURERS SPECIFICATION. WOULD YOU PLEASE MOVE |
| | THE PUMP ROOM LABEL SO IT CAN BE READ FOR CLARITY? |
| | WOULD YOU PLEASE SHOW THE FORCE DRAIN DUMPING INTO THE |
| | FD PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | G. IN THE LOBBY AREA, THERE WERE TWO RESTROOMS AND ONE |
| | DRINKING FOUNTAIN DELETED. ARE THEY PART OF THE POOL |
| | AREA CONFIGURATION? WOULD YOU PLEASE CLARIFY PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? IF SO, WHERE WERE THEY LOCATED |
| | TOO? |
| | |
| | H. IN THE DROP-OFF LOBBY, THERE IS A STORM DRAIN IN THE |
| | STAIRWELL IN THE PREVIOUS CONFIGURATION, AND NOW THE |
| | STAIRWELL MOVED BUT DID THE FLOOR DRAIN NEED TO MOVE AS |
| | WELL. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | I. ON SDS/1 THAT POINTS TO THE PACKAGE LOCKERS, THERE |
| | IS A CURB STOP OVER IT. WOULD YOU PLEASE MOVE IT FOR |
| | CLARITY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | J. THERE ARE ITEMS MOVED AROUND AND LABELS ON TOP OF |
| | EACH OTHER ON THIS AND THE PREVIOUS PAGES. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | L. NEXT TO THE LOBBY, IT HAS THE DROP-OFF AREA AND |
| | DOORS THAT ARE MISSING WALLS. WOULD YOU PLEASE CORRECT |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 3. ON SHEET P201N-CLG; |
| | A. THERE ARE TWO VEHICLES, AND ONE IS OVER THE VERBIAGE |
| | FOR THE 6? RD. WOULD YOU PLEASE MOVE IT FOR CLARITY PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. EMPLOYEE BREAKROOM NOT LABELED. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 4. ON SHEET P201S-CLG; |
| | A. THERE IS A MECHANICAL AND PLUMBING SECTION FOR |
| | CONCRETE IN THE POOL AREA THAT IS FLOATING AND DOES NOT |
| | NEED TO BE THERE. WOULD YOU PLEASE REMOVE IT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. IN THE JANITORS ROOM AREA, WORDS ARE ON TOP OF EACH |
| | OTHER AND NOT LEGIBLE. WOULD YOU PLEASE CORRECT THEM BY |
| | MOVING THEM SO THEY CAN BE READ PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | C. THERE ARE HOSE BIBBS SHOWN IN THE NEW RESTROOMS, AND |
| | THERE IS NO ISOMETRIC THAT SHOWS A WATER DISTRIBUTION |
| | REVISION FOR THE SOUTH TOWER. WOULD YOU PLEASE PROVIDE |
| | ONE AND SHOW THE SHUT OFF VALVES FOR THE HOSE BIBBS PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | 5. ON SHEET P2.02N; |
| | A. RN/9 UNIT S1 IS POINTING TO A DOOR THEY HAVE BEEN |
| | MOVED BEHIND THE WASHING MACHINE. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF |
| | THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | C. IN STAIRWELL 1, THERE ARE TWO NEW LIGHTS THE ARE |
| | OVER S/N 11,13 AND SN/2. WOULD YOU PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING |
| | MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 6. ON SHEET P2.02S |
| | A. RS/9 UNIT S1 IS POINTING TO A DOOR THEY HAVE BEEN |
| | MOVED BEHIND AHU. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING |
| | MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | C. IN STAIRWELL 3, THERE ARE TWO NEW LIGHTS THE ARE |
| | OVER S/S 1 AND NOTE 1. WOULD YOU PLEASE CORRECT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 7. ON SHEET P2.02NA AND P2.02NB; |
| | A. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING |
| | MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. IN-UNIT A-4, THE STACK FOR THE WASHING MACHINE AND |
| | BATHROOM ARE NOT LABELED. WOULD YOU PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF |
| | THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? NOT IN P2.02 NB |
| | |
| | D. IN STAIRWELL 1, THERE ARE TWO NEW LIGHTS THE ARE |
| | OVER S/N 11,13 AND SN/2. WOULD YOU PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? NOT IN P2.02 NB |
| | |
| | 8. ON SHEET P2.02SA P2.02 SB; |
| | A. ON UNIT C1 THE WATER LINE IN THE SHOWER IS NOT IN |
| | THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? IN P2.02 SB, THE SHOWER LAYOUT |
| | IS DIFFERENT. IS THIS TYPICAL OF ALL OTHER UNITS UP AND |
| | DOWN. WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | B. IN-UNIT A-4, THE STACK FOR THE WASHING MACHINE AND |
| | BATHROOM ARE NOT LABELED. WOULD YOU PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. SN/31 UNIT A-1 IS MISSING A WALL IN THE WASHING |
| | MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 9. ON SHEET P2.03N, SN/34 UNIT A-1 IS MISSING A WALL IN |
| | THE WASHING MACHINE AREA. WOULD YOU PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | 10. ON SHEET P2.03S; |
| | A. IN STAIRWELL 3, THERE IS ONE NEW LIGHT THAT IS OVER |
| | NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING |
| | MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | C. ON UNIT C1 THE WATER LINE IN THE SHOWER IS NOT IN |
| | THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 11. ON SHEET P2.04N; |
| | A. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING |
| | MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF |
| | THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 12. ON SHEET 2.04S; |
| | A. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING |
| | MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. NO SHOWER HEAD LOCATION SHOWN IN THE ENTIRE DRAWING, |
| | WHICH WILL NEED TO COMPLY WITH THE FAIR HOUSING ACT |
| | LOCATION SHOWN ON OTHER FLOORS. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 13. ON SHEET 2.05N; |
| | A. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING |
| | MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF |
| | THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | C. IN STAIRWELL 1, THERE ARE TWO NEW LIGHTS THE ARE |
| | OVER S/N 11. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | D. ON STAIRWELL 2, THERE IS ONE NEW LIGHT THAT IS OVER |
| | NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 14. ON SHEET 2.05S; |
| | A. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING |
| | MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. IN STAIRWELL 3, THERE IS ONE NEW LIGHT THAT IS OVER |
| | NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 15. ON SHEET P2.06; |
| | A. IN STAIRWELL 3, THERE IS ONE NEW LIGHT THAT IS OVER |
| | NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 16. ON SHEET 4.05N; |
| | A. NUMBER 37 ON ISOMETRIC IS MISSING AIR ARRESTORS ON |
| | ICEMAKER AND SINK. WHERE THEY REMOVED AS THEY ARE |
| | REQUIRED ON ICEMAKER. WOULD YOU PLEASE CORRECT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. IN NUMBER 28, THE AIR ARRESTOR HAS BEEN REMOVED AND |
| | THE WATER COOLER AND REQUIRED ON THE WATER COOLER. IN |
| | THAT SAME BATHROOM GROUP, IT SHOWS TWO HOSE BIBBS AND |
| | ONE SHUT OFF. EACH SILLCOCK SHALL HAVE ITS OWN SHUT-OFF |
| | PER THE 2017 FBC SECTION 606.2 (2) LOCATION OF SHUTOFF |
| | VALVES. THEY SHALL BE ACCESSIBLE. |
| | |
| | 17. ON SHEET 4 P4.11N; |
| | A. THE GAS CHART HAS BEEN DELETED. WOULD YOU PLEASE |
| | PROVIDE OR PUT A NOTE PER THE 2017 FBC FG SEC. 402.3? |
| | |
| | B. THERE WERE TWO BBQ UNITS SHOWN IN THE NEW REVISION, |
| | FOUR SHOWN IN THE POOL AREA. ARE THESE BBQ?S NOT |
| | INCLUDED IN THE REVISED GAS SYSTEM BUT ARE IN THE |
| | KEYNOTES? ARE THEY THE PROPANE TANK TYPE? WOULD YOU |
| | PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. IN GENERAL NOTES, COLOR DETECTION TAPE IS NOT |
| | APPROVED AN APPROVED BY THE LOCAL AJH. AN 18? GAUGE |
| | WIRE, A YELLOW INSULATED COPPER TRACER WIRE, WILL BE |
| | REQUIRED PER THE 2017 FBC SEC. 404.17.3. |
| | |
| | D. THE NEW FOUR BBQ SEEM TO BE ENCLOSED AND MAY REQUIRE |
| | HOOD VENT PER THE MANUFACTURERS SPECIFICATION. IF THAT |
| | IS THE CASE, PLEASE PROVIDE SPECIFICATIONS OR MAKE |
| | NOTES ON PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | E. CSST PIPE IN THE SLEEVE WILL REQUIRE VENTING PER THE |
| | AJH AND AS SHOWN ON THE MANUFACTURES SPECIFICATION. |
| | PLEASE PROVIDE A NOTE UNDER GENERAL NOTES PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | F. ON THE FUTURE SERVICES, IT SAYS TWO SERVICES, BUT |
| | PLANS SHOW THREE. WOULD YOU PLEASE CLARIFY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 18. ON SHEET P5.01S; |
| | A. THE SANITARY FOR THE SINK IN THE POOL AREA HAS BEEN |
| | MOVED, AND THE NEW LOCATION IS NOT SHOWN. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. IN THE NORTH TOWER, THE SINK FOR THE POOL AREA, WAS |
| | ALSO MOVED, AND NO ISOMETRIC FOR SANITARY OR WATER WAS |
| | SHOWN. WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | C. PLEASE PROVIDE THE LOCATION FOR THE SHOWER OUTSIDE |
| | AND CONNECTION TO DRAINAGE PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | 19. ON SHEET P5.05P; |
| | A. LOBBY RESTROOM HAS A HOSE BIBB, AND IT REQUIRES A |
| | SHUTOFF VALVE ON THE SILLCOCK PER THE 2017 FBC SEC. P |
| | 606.2 (2). |
| | |
| | B. THE PUMP SHOWS CONDENSATE (CD) DARING INTO THE |
| | SANITARY PER THE CITY OF WEST PALM BEACH IT IS NOT |
| | ALLOWED. WOULD YOU PLEASE PROVIDE DRAINAGE TO THE |
| | OUTSIDE OF THE STORM PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. PLEASE PROVIDE ISOLATION BACKFLOW ON MECHANICAL |
| | EQUIPMENT (PUMP, IRRIGATION POOL PUMP, CHILLER, ETC.) |
| | PER THE 2017 FBC TABLE 608.1. |
| | |
| | D. THE MAINTENANCE RESTROOM SHOWS A HOSE BIBB ON SHEET |
| | 201S CELLING BUT NOT SHOWN ON ISOMETRIC, REQUIRING A |
| | SILLCOCK. WOULD YOU PLEASE PROVIDE AN ISOMETRIC PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 20. ON SHEET P5.07S ON DETAIL 1 SHOWS TWO DOUBLE HOSE |
| | BIBBS ON LEVEL 25, AND EACH SHALL BE ON ITS OWN |
| | SILLCOCK PER THE 2017 FBC SEC. P 606.2 (2). |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |