Plan Review Notes
Plan Review Notes For Permit 21060844
Permit Number 21060844
Review Stop P
Sequence Number 1
Notes
Date Text
2021-07-19 17:10:2007/19/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET 2.01N;
 A. THE RESTROOM WAS MOVED, AND N-105 A LABEL IS NOT
 PRESENT. WOULD YOU PLEASE LABEL PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 B. THE SINK IN THE MULTI-PURPOSE ROOM IS NOT SHOWN, AND
 NEITHER ARE THE REFRIGERATOR AND ICE MACHINE. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. THE SINK LAYOUT, BBQ, AND SHOWER ARE NOT SHOWN, AND
 THE SANITARY IS STILL SHOWS. WHERE WERE THEY MOVE TO?
 WOULD YOU PLEASE SHOW THE NEW LOCATION AND LABEL PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 D. IT SHOWS TWO BBQ AND A SINK IN A DIFFERENT LOCATION.
 WOULD YOU PLEASE PROVIDE THE DRAINAGE AND GAS TO IT? IF
 THE BBQ IS ENCLOSED IN A ROOM, THEY MAY REQUIRE A HOOD
 SYSTEM. THAT WILL NEED TO BE DETERMINED AND NOTED ON
 PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 E. PUMP ROOM/ MECHANICAL ROOM, NOT LABELS AND WORD PUMP
 ROOM NOT TOO VISIBLE WOULD YOU PLEASE MOVE AND LABEL
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 F. THE STORM HAS 16,820 SF 874 GPM IN THE PREVIOUS
 VERSION; NOW, IT HAS 7,990 419 GPM, AND THERE ARE TWO
 8? SD DELETED. IF SO, PLEASE CLARIFY HOW THIS WATER
 WILL BE CAUGHT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 G. IN THE RESIDENTIAL ACTIVE USE AREA, THERE ARE WALLS
 MISSING WALLS ALL THE WAY UP TO THE STAFF LOCKER. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 2. ON SHEET 2.01S;
 A. IN THE RESIDENTIAL ACTIVE USE AREA, THERE ARE WALLS
 MISSING WALLS. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. ON KEYNOTE 15 BY POOL EQUIPMENT SAYS IT IS A
 CONTINUATION OF P201N. THAT IS NOT AN APPARENT
 REFERENCE TO THAT NUMBER. WOULD YOU PLEASE CORRECT OR
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. IN THE TRASH ROOM AREA, PLEASE LABEL THE 4-INCH
 FLOOR DRAIN WITH A REMOVABLE BASKET PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. IT SHOWS TWO BBQ AND A SINK IN A DIFFERENT LOCATION.
 WOULD YOU PLEASE PROVIDE THE DRAINAGE AND GAS TO IT? IF
 THE BBQ IS ENCLOSED IN A ROOM, THEY MAY REQUIRE A HOOD
 SYSTEM. THIS WILL NEED TO BE DETERMINED AND NOTED ON
 PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. THE SINK IN THE MULTI-PURPOSE ROOM IS NOT SHOWN, AND
 NEITHER ARE THE REFRIGERATOR AND ICE MACHINE. THERE IS
 A WALL MISSING AS WELL. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS? PLEASE MOVE THE LABEL FOR
 THE MULTI-PURPOSE ROOM OVER AS IT HAS THE WATER LINES
 OVER IT.
  
 E. NUMBER 25 ON STAIRWELL 4 HAS A STORM DRAIN IN A
 STAIRWELL. IF THIS IS A PRESSURIZED STAIRWELL, IT IS
 NOT ALLOWED UNLESS IT IS IN A CHASE. WOULD YOU PLEASE
 CLARIFY OR MOVE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 F. PUMP ROOM WAS MOVED, AND THERE SEEMS TO BE ONE SIDE
 THAT DOES NOT HAVE THE INCHES REQUIRED IN CLEARANCE PER
 THE MANUFACTURERS SPECIFICATION. WOULD YOU PLEASE MOVE
 THE PUMP ROOM LABEL SO IT CAN BE READ FOR CLARITY?
 WOULD YOU PLEASE SHOW THE FORCE DRAIN DUMPING INTO THE
 FD PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 G. IN THE LOBBY AREA, THERE WERE TWO RESTROOMS AND ONE
 DRINKING FOUNTAIN DELETED. ARE THEY PART OF THE POOL
 AREA CONFIGURATION? WOULD YOU PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? IF SO, WHERE WERE THEY LOCATED
 TOO?
  
 H. IN THE DROP-OFF LOBBY, THERE IS A STORM DRAIN IN THE
 STAIRWELL IN THE PREVIOUS CONFIGURATION, AND NOW THE
 STAIRWELL MOVED BUT DID THE FLOOR DRAIN NEED TO MOVE AS
 WELL. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 I. ON SDS/1 THAT POINTS TO THE PACKAGE LOCKERS, THERE
 IS A CURB STOP OVER IT. WOULD YOU PLEASE MOVE IT FOR
 CLARITY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 J. THERE ARE ITEMS MOVED AROUND AND LABELS ON TOP OF
 EACH OTHER ON THIS AND THE PREVIOUS PAGES. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 L. NEXT TO THE LOBBY, IT HAS THE DROP-OFF AREA AND
 DOORS THAT ARE MISSING WALLS. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 3. ON SHEET P201N-CLG;
 A. THERE ARE TWO VEHICLES, AND ONE IS OVER THE VERBIAGE
 FOR THE 6? RD. WOULD YOU PLEASE MOVE IT FOR CLARITY PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 B. EMPLOYEE BREAKROOM NOT LABELED. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 4. ON SHEET P201S-CLG;
 A. THERE IS A MECHANICAL AND PLUMBING SECTION FOR
 CONCRETE IN THE POOL AREA THAT IS FLOATING AND DOES NOT
 NEED TO BE THERE. WOULD YOU PLEASE REMOVE IT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. IN THE JANITORS ROOM AREA, WORDS ARE ON TOP OF EACH
 OTHER AND NOT LEGIBLE. WOULD YOU PLEASE CORRECT THEM BY
 MOVING THEM SO THEY CAN BE READ PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 C. THERE ARE HOSE BIBBS SHOWN IN THE NEW RESTROOMS, AND
 THERE IS NO ISOMETRIC THAT SHOWS A WATER DISTRIBUTION
 REVISION FOR THE SOUTH TOWER. WOULD YOU PLEASE PROVIDE
 ONE AND SHOW THE SHUT OFF VALVES FOR THE HOSE BIBBS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 5. ON SHEET P2.02N;
 A. RN/9 UNIT S1 IS POINTING TO A DOOR THEY HAVE BEEN
 MOVED BEHIND THE WASHING MACHINE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. IN STAIRWELL 1, THERE ARE TWO NEW LIGHTS THE ARE
 OVER S/N 11,13 AND SN/2. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 D. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 6. ON SHEET P2.02S
 A. RS/9 UNIT S1 IS POINTING TO A DOOR THEY HAVE BEEN
 MOVED BEHIND AHU. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. IN STAIRWELL 3, THERE ARE TWO NEW LIGHTS THE ARE
 OVER S/S 1 AND NOTE 1. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 7. ON SHEET P2.02NA AND P2.02NB;
 A. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. IN-UNIT A-4, THE STACK FOR THE WASHING MACHINE AND
 BATHROOM ARE NOT LABELED. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 C. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? NOT IN P2.02 NB
  
 D. IN STAIRWELL 1, THERE ARE TWO NEW LIGHTS THE ARE
 OVER S/N 11,13 AND SN/2. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS? NOT IN P2.02 NB
  
 8. ON SHEET P2.02SA P2.02 SB;
 A. ON UNIT C1 THE WATER LINE IN THE SHOWER IS NOT IN
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? IN P2.02 SB, THE SHOWER LAYOUT
 IS DIFFERENT. IS THIS TYPICAL OF ALL OTHER UNITS UP AND
 DOWN. WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 B. IN-UNIT A-4, THE STACK FOR THE WASHING MACHINE AND
 BATHROOM ARE NOT LABELED. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 C. SN/31 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 9. ON SHEET P2.03N, SN/34 UNIT A-1 IS MISSING A WALL IN
 THE WASHING MACHINE AREA. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 10. ON SHEET P2.03S;
 A. IN STAIRWELL 3, THERE IS ONE NEW LIGHT THAT IS OVER
 NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. ON UNIT C1 THE WATER LINE IN THE SHOWER IS NOT IN
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 11. ON SHEET P2.04N;
 A. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 12. ON SHEET 2.04S;
 A. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. NO SHOWER HEAD LOCATION SHOWN IN THE ENTIRE DRAWING,
 WHICH WILL NEED TO COMPLY WITH THE FAIR HOUSING ACT
 LOCATION SHOWN ON OTHER FLOORS. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 13. ON SHEET 2.05N;
 A. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. IN STAIRWELL 1, THERE ARE TWO NEW LIGHTS THE ARE
 OVER S/N 11. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 D. ON STAIRWELL 2, THERE IS ONE NEW LIGHT THAT IS OVER
 NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 14. ON SHEET 2.05S;
 A. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. IN STAIRWELL 3, THERE IS ONE NEW LIGHT THAT IS OVER
 NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 15. ON SHEET P2.06;
 A. IN STAIRWELL 3, THERE IS ONE NEW LIGHT THAT IS OVER
 NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 16. ON SHEET 4.05N;
 A. NUMBER 37 ON ISOMETRIC IS MISSING AIR ARRESTORS ON
 ICEMAKER AND SINK. WHERE THEY REMOVED AS THEY ARE
 REQUIRED ON ICEMAKER. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. IN NUMBER 28, THE AIR ARRESTOR HAS BEEN REMOVED AND
 THE WATER COOLER AND REQUIRED ON THE WATER COOLER. IN
 THAT SAME BATHROOM GROUP, IT SHOWS TWO HOSE BIBBS AND
 ONE SHUT OFF. EACH SILLCOCK SHALL HAVE ITS OWN SHUT-OFF
 PER THE 2017 FBC SECTION 606.2 (2) LOCATION OF SHUTOFF
 VALVES. THEY SHALL BE ACCESSIBLE.
  
 17. ON SHEET 4 P4.11N;
 A. THE GAS CHART HAS BEEN DELETED. WOULD YOU PLEASE
 PROVIDE OR PUT A NOTE PER THE 2017 FBC FG SEC. 402.3?
  
 B. THERE WERE TWO BBQ UNITS SHOWN IN THE NEW REVISION,
 FOUR SHOWN IN THE POOL AREA. ARE THESE BBQ?S NOT
 INCLUDED IN THE REVISED GAS SYSTEM BUT ARE IN THE
 KEYNOTES? ARE THEY THE PROPANE TANK TYPE? WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. IN GENERAL NOTES, COLOR DETECTION TAPE IS NOT
 APPROVED AN APPROVED BY THE LOCAL AJH. AN 18? GAUGE
 WIRE, A YELLOW INSULATED COPPER TRACER WIRE, WILL BE
 REQUIRED PER THE 2017 FBC SEC. 404.17.3.
  
 D. THE NEW FOUR BBQ SEEM TO BE ENCLOSED AND MAY REQUIRE
 HOOD VENT PER THE MANUFACTURERS SPECIFICATION. IF THAT
 IS THE CASE, PLEASE PROVIDE SPECIFICATIONS OR MAKE
 NOTES ON PLANS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. CSST PIPE IN THE SLEEVE WILL REQUIRE VENTING PER THE
 AJH AND AS SHOWN ON THE MANUFACTURES SPECIFICATION.
 PLEASE PROVIDE A NOTE UNDER GENERAL NOTES PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. ON THE FUTURE SERVICES, IT SAYS TWO SERVICES, BUT
 PLANS SHOW THREE. WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 18. ON SHEET P5.01S;
 A. THE SANITARY FOR THE SINK IN THE POOL AREA HAS BEEN
 MOVED, AND THE NEW LOCATION IS NOT SHOWN. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. IN THE NORTH TOWER, THE SINK FOR THE POOL AREA, WAS
 ALSO MOVED, AND NO ISOMETRIC FOR SANITARY OR WATER WAS
 SHOWN. WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 C. PLEASE PROVIDE THE LOCATION FOR THE SHOWER OUTSIDE
 AND CONNECTION TO DRAINAGE PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 19. ON SHEET P5.05P;
 A. LOBBY RESTROOM HAS A HOSE BIBB, AND IT REQUIRES A
 SHUTOFF VALVE ON THE SILLCOCK PER THE 2017 FBC SEC. P
 606.2 (2).
  
 B. THE PUMP SHOWS CONDENSATE (CD) DARING INTO THE
 SANITARY PER THE CITY OF WEST PALM BEACH IT IS NOT
 ALLOWED. WOULD YOU PLEASE PROVIDE DRAINAGE TO THE
 OUTSIDE OF THE STORM PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. PLEASE PROVIDE ISOLATION BACKFLOW ON MECHANICAL
 EQUIPMENT (PUMP, IRRIGATION POOL PUMP, CHILLER, ETC.)
 PER THE 2017 FBC TABLE 608.1.
  
 D. THE MAINTENANCE RESTROOM SHOWS A HOSE BIBB ON SHEET
 201S CELLING BUT NOT SHOWN ON ISOMETRIC, REQUIRING A
 SILLCOCK. WOULD YOU PLEASE PROVIDE AN ISOMETRIC PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 20. ON SHEET P5.07S ON DETAIL 1 SHOWS TWO DOUBLE HOSE
 BIBBS ON LEVEL 25, AND EACH SHALL BE ON ITS OWN
 SILLCOCK PER THE 2017 FBC SEC. P 606.2 (2).
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  