| 2021-07-15 08:04:32 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21060844 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE |
| | CHANGED FLOOR PLAN FOR SHEET M2.01S |
| | |
| | 2) SHEET M2.01G- PLEASE PROVIDE MECHANICAL EQUIPMENT |
| | SIZING CALCULATIONS FOR THIS NEW HP-G1.6. |
| | |
| | 3) SHEET M2.01G- PLEASE PROVIDE OUTDOOR AIR |
| | CALCULATIONS FOR THE NEW HP-G1.6 AND SHOW HOW THE |
| | OUTDOOR AIR WILL BE PROVIDED. |
| | |
| | 4) SHEET M2.01N- PLEASE EXPLAIN THE MISSING SPF-1-1 IN |
| | THE STAIRWAY. |
| | |
| | 5) SHEET M3.01- UNIT A3 THE DRYER DUCT ROUTE HAS |
| | CHANGED WHICH NOW SHOWS 6 90 DEGREE ELBOWS. PLEASE |
| | PROVIDE DRYER MANUFACTURE INSTALLATION INSTRUCTIONS |
| | SHOWING THAT THIS MANY 90 DEGREE ELBOWS ARE ALLOWED FOR |
| | THE SPECIFIC DRYER USED. FBC M 504.8.4.2 |
| | |
| | 6) SHEET M3.02- UNIT B6-THE NEW PATH FOR THE DRYER |
| | EXHAUST DUCT HAS CHANGED. PLEASE PROVIDE THE NEW DUCT |
| | LENGTH. FBC M 504.8.4.2 |
| | |
| | 7) SHEET M3.02- UNIT B1- PLEASE PROVIDE THE NEW DRYER |
| | DUCT LENGTH. FBC M 504.8.4.2 |
| | |
| | 8) SHEET M3.02- UNIT A2- THE NEW DRYER DUCT PATH HAS 7 |
| | 90 DEGREE TURNS IN THE DUCT. PLEASE PROVIDE |
| | INSTALLATION INSTRUCTIONS FROM THE DRYER MANUFACTURER |
| | STATING THAT THE DUCT WORK CAN HAVE THIS MANY 90 DEGREE |
| | TURNS. |
| | |
| | 9) SHEET M3.03- UNIT C1- PLEASE SHOW DRYER DUCT LENGTH |
| | AND PROVIDE INFORMATION FROM DRYER MANUFACTURER THAT 5 |
| | 90 DEGREE ELBOWS ARE ALLOWED IN THE DRYER DUCT. FBC M |
| | 504.8.4.2 |
| | |
| | 10) SHEET M3.03- UNIT B5- PLEASE PROVIDE DEVELOPMENTAL |
| | LENGTH OF THE DRYER DUCT. FBC M 504.8.4.2 |
| | |
| | 11) SHEET M3.03- UNIT B4- PLEASE PROVIDE THE DEVELOPED |
| | LENGTH OF DRYER DUCT AND INFORMATION FROM DRYER |
| | MANUFACTURER ALLOWING THE NUMBER OF 90 DEGREE ELBOWS |
| | SHOW ON THE DRAWING. FBC M 504.8.4.2 |
| | |
| | 12) SHEET M4.02- PLEASE PROVIDE OUTDOOR AIR |
| | CALCULATIONS BASED ON 2017 FBC M 403.3.1.1 AND TABLE |
| | 403.3.1.1. AS AN ALTERNATE MEANS AND METHODS YOU CAN |
| | SUBMIT A COMPLETE DESIGN BASED ON THE ASHRAE 62.1-2013. |
| | THIS WOULD MEAN A COMPLETE DESIGN NOT JUST THE OUTDOOR |
| | AIR CALCULATIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |