Plan Review Notes
Plan Review Notes For Permit 21060844
Permit Number 21060844
Review Stop M
Sequence Number 1
Notes
Date Text
2021-07-15 08:04:321ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21060844
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE
 CHANGED FLOOR PLAN FOR SHEET M2.01S
  
 2) SHEET M2.01G- PLEASE PROVIDE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS FOR THIS NEW HP-G1.6.
  
 3) SHEET M2.01G- PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS FOR THE NEW HP-G1.6 AND SHOW HOW THE
 OUTDOOR AIR WILL BE PROVIDED.
  
 4) SHEET M2.01N- PLEASE EXPLAIN THE MISSING SPF-1-1 IN
 THE STAIRWAY.
  
 5) SHEET M3.01- UNIT A3 THE DRYER DUCT ROUTE HAS
 CHANGED WHICH NOW SHOWS 6 90 DEGREE ELBOWS. PLEASE
 PROVIDE DRYER MANUFACTURE INSTALLATION INSTRUCTIONS
 SHOWING THAT THIS MANY 90 DEGREE ELBOWS ARE ALLOWED FOR
 THE SPECIFIC DRYER USED. FBC M 504.8.4.2
  
 6) SHEET M3.02- UNIT B6-THE NEW PATH FOR THE DRYER
 EXHAUST DUCT HAS CHANGED. PLEASE PROVIDE THE NEW DUCT
 LENGTH. FBC M 504.8.4.2
  
 7) SHEET M3.02- UNIT B1- PLEASE PROVIDE THE NEW DRYER
 DUCT LENGTH. FBC M 504.8.4.2
  
 8) SHEET M3.02- UNIT A2- THE NEW DRYER DUCT PATH HAS 7
 90 DEGREE TURNS IN THE DUCT. PLEASE PROVIDE
 INSTALLATION INSTRUCTIONS FROM THE DRYER MANUFACTURER
 STATING THAT THE DUCT WORK CAN HAVE THIS MANY 90 DEGREE
 TURNS.
  
 9) SHEET M3.03- UNIT C1- PLEASE SHOW DRYER DUCT LENGTH
 AND PROVIDE INFORMATION FROM DRYER MANUFACTURER THAT 5
 90 DEGREE ELBOWS ARE ALLOWED IN THE DRYER DUCT. FBC M
 504.8.4.2
  
 10) SHEET M3.03- UNIT B5- PLEASE PROVIDE DEVELOPMENTAL
 LENGTH OF THE DRYER DUCT. FBC M 504.8.4.2
  
 11) SHEET M3.03- UNIT B4- PLEASE PROVIDE THE DEVELOPED
 LENGTH OF DRYER DUCT AND INFORMATION FROM DRYER
 MANUFACTURER ALLOWING THE NUMBER OF 90 DEGREE ELBOWS
 SHOW ON THE DRAWING. FBC M 504.8.4.2
  
 12) SHEET M4.02- PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS BASED ON 2017 FBC M 403.3.1.1 AND TABLE
 403.3.1.1. AS AN ALTERNATE MEANS AND METHODS YOU CAN
 SUBMIT A COMPLETE DESIGN BASED ON THE ASHRAE 62.1-2013.
 THIS WOULD MEAN A COMPLETE DESIGN NOT JUST THE OUTDOOR
 AIR CALCULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  