2021-07-19 17:13:1107/19/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 ON SHEET 4 P4.11N;
  
 A. THE GAS CHART HAS BEEN DELETED. WOULD YOU PLEASE
 PROVIDE OR PUT A NOTE PER THE 2017 FBC FG SEC. 402.3?
  
 B. THERE WERE TWO BBQ UNITS SHOWN IN THE NEW REVISION,
 FOUR SHOWN IN THE POOL AREA. ARE THESE BBQ?S NOT
 INCLUDED IN THE REVISED GAS SYSTEM BUT ARE IN THE
 KEYNOTES? ARE THEY THE PROPANE TANK TYPE? WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. IN GENERAL NOTES, COLOR DETECTION TAPE IS NOT
 APPROVED AN APPROVED BY THE LOCAL AJH. AN 18? GAUGE
 WIRE, A YELLOW INSULATED COPPER TRACER WIRE, WILL BE
 REQUIRED PER THE 2017 FBC SEC. 404.17.3.
  
 D. THE NEW FOUR BBQ SEEM TO BE ENCLOSED AND MAY REQUIRE
 HOOD VENT PER THE MANUFACTURERS SPECIFICATION. IF THAT
 IS THE CASE, PLEASE PROVIDE SPECIFICATIONS OR MAKE
 NOTES ON PLANS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. CSST PIPE IN THE SLEEVE WILL REQUIRE VENTING PER THE
 AJH AND AS SHOWN ON THE MANUFACTURES SPECIFICATION.
 PLEASE PROVIDE A NOTE UNDER GENERAL NOTES PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. ON THE FUTURE SERVICES, IT SAYS TWO SERVICES, BUT
 PLANS SHOW THREE. WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  