| Plan Review Notes For Permit 21060842 |
| Permit Number |
21060842 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-02 08:18:18 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) INDICATE THE AREAS THAT THE FLOORING AND SOUND | | | INSULATION WILL BE INSTALLED ON THE FLOOR PLAN. | | | INDICATE THE ADDRESS AND UNIT NUMBER ON THE FLOOR PLAN. | | | THE PERSON PROVIDING THE INFORMATION ON THE DRAWING IS | | | TO PRINT THEIR NAME AND SIGN IT. FBC AMENDMENTS 107.2.1 | | | | | | 2) SUBMIT A TEST REPORT FOR THE SUPER SIM 90 FOR | | | STRUCTURE-BORNE SOUND, ASTM E 492-09, WITHOUT THE | | | SUSPENDED CEILING AND INSULATION BELOW THE SLAB. FBC | | | AMEND.107.2.1 & FBC 1207.3 | | | | | | 3) SUBMIT THE SPECIFICATIONS FOR THE PROPOSED LUX VINYL | | | FLOOR COVERING. FBC AMEND.107.2.1 | | | |
|