Plan Review Notes
Plan Review Notes For Permit 21060769
Permit Number 21060769
Review Stop E
Sequence Number 1
Notes
Date Text
2021-06-16 15:25:25ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PANEL CAN NOT BE IN A CLOSET.
  
 240.24(D) NOT IN VICINITY OF EASILY IGNITIBLE MATERIAL.
 OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE
 VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN
 CLOTHES CLOSETS.
  
 2) OUTLET REQUIRED AT THE FRONT AND REAR OF UNIT
 OUTSIDE.
  
 210.52(E)(1) ONE-FAMILY AND TWO-FAMILY DWELLINGS. FOR A
 ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY
 DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE
 RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND NOT
 MORE THAN 2.0 M (6 1?2 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
  