| 2021-08-24 14:10:33 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21060762 |
| | ADD: 630 S. SAPODILLA AVE. # 315 |
| | CONT: TRI COUNTY RESTORATION |
| | TEL: 561-232-7713 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. AUGUST 24TH/2021 |
| | ACTION: DENIED |
| | |
| | NOTICE !!! 4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B) WITH RESPECT TO EVALUATION OF DESIGN |
| | PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS |
| | IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE |
| | FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| | REVIEW. |
| | |
| | |
| | 1) 2ND REVIEW. SHEET A100 COVERSHEET: |
| | 1A) 2ND REVIEW. THE COVERSHEET LIST THE ALTERATION AS A |
| | LEVEL I ALTERATION. PLEASE NOTE LEVEL I IS CHANGEOUT OF |
| | MATERIALS LIKE FOR LIKE. THIS ALTERATION IS CONSIDERED |
| | A LEVEL II ALTERATION SINCE FOR ONE YOU ARE REMOVING |
| | TUB AND CREATING A NEW SHOWER. 2020 EXISTING BUILDING |
| | CODE. 801.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1B) 2ND REVIEW. THE CONSTRUCTION TYPE IS LISTED AS TYPE |
| | VB. PLEASE NOTE THIS IS A MULTISTORY CONDOMINIUM SEE |
| | TABLE 504.4 OF THE 2020 FBC-B. NOTE THIS IS A 5-STORY |
| | RESIDENTIAL BUILDING. |
| | |
| | 1C) 2ND REVIEW. THE COVERSHEET LISTS THE OCCUPANCY TYPE |
| | AS R-3. R-3 OCCUPANCIES ARE FOR SINGLE FAMILY |
| | RESIDENCES NOT MULTI STORY EITHER APARTMENT BUILDINGS |
| | OR CONDOMINIUMS. 2020 FBC-B SECTION 310 R-2 OCCUPANCY. |
| | |
| | 2) SHEET A102: |
| | 2) COMPLIED. |
| | |
| | 3) 2ND REQUEST. THE FLOOR PLAN ALSO NOTES NEW TILE / |
| | MARBLE FLOORING. FLOOR INSULATION/ UNDERLAYMENT (FBC-B |
| | 2020) FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING |
| | ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED |
| | FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET |
| | THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS |
| | FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED |
| | CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 3A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 3B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 3C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1. |
| | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |