Plan Review Notes
Plan Review Notes For Permit 21060690
Permit Number 21060690
Review Stop P
Sequence Number 1
Notes
Date Text
2021-07-20 14:20:241ST REVIEW FBC-2020 PLUMBING
 PERMIT-21060690
 7/20/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET D-1: SHOW THE LOCATIONS OF THE REMOVE PLUMBING
 FIXTURES PER KEY NOTE #3- SECTION 107.2.1 WPB.
  
 2) A-1: GENERAL NOTE #2 WHICH STATES THAT PVC IS
 ALLOWED IN PLENUM SPACES APPEARS TO BE INCORRECT.
 PLEASE PROVIDE A MANUFACTURER'S PRODUCT DATA FOR PVC
 PIPING TO BE USED ON THE PROJECT TO VERIFY IT IS
 PLENUM-RATED- SECTION 107.2.1 WPB.
  
 3) P-1: THE NEW SK-1 & 2 BRANCH DRAIN IS NOT PERMITTED
 TO CONNECT INTO THE EXISTING WET VENT FOR THE BATHROOM-
 SECTION 912.1 FBC P. IN ACCORDANCE WITH THE SECTION,
 THE BRANCH DRAIN SHALL CONNECT DOWNSTREAM OF THE WET
 VENT- PLEASE CORRECT.
  
 3) P-1: REFER TO SECTION C404.5.1 AND TABLE C404.5.1
 FBC ENERGY CONSERVATION- THE DRAWINGS APPEAR TO SHOW
 THE LENGTHS OF THE 1/2-INCH HOT WATER SUPPLY PIPES FROM
 THE WATER HEATER TO THE LAVATORIES IS EXCEEDING THE
 MAXIMUM ALLOWABLE LENGTHS OF 2FT. EITHER POINT OF USE
 WATER HEATERS AT THE LAVATORIES OR A RECIRCULATION PUMP
 FOR THE HOT WATER SYSTEM SHALL BE INSTALLED.
  
 4) P-1: SHOW THE WATER HEATER PAN DRAIN LINE RUN AND
 DISCHARGE LOCATION- SECTIONS 504.7.1 & 504.7.2- THE PAN
 DRAIN SHALL EXTEND FULL SIZE AND TERMINATE OVER A
 SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR DRAIN
 OR EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE
 NOT LESS THAN 6 INCHES AND NOT MORE THAN 24 INCHES
 ABOVE THE ADJACENT GROUND SURFACE.
  
 5) A-1, A-3, P-1: REFER TO SECTION 212.3 FBC ACC- WHERE
 SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER
 THAN ONE, OF EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM
 OR SPACE SHALL COMPLY WITH 606. PLEASE SHOW THE CLEAR
 FLOOR SPACE DIAGRAMS AND DIMENSIONS AT SK-1 & SK-2AND
 PROVIDE AN ELEVATION DRAWING SHOWING SINK RIM HEIGHTS
 AND KNEE AND TOE CLEARANCES- SECTIONS 606.2 & 606.3 FBC
 P. THE CURRENT PLANS AND DETAILS ARE NOT IN COMPLIANCE.
  
 6) D-1: WHERE SLAB DEMOLITION IS NECESSARY, OUTLINE THE
 AREAS AND PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1
 WPB.
  
 7) P-1: PROVIDE COMPLETE DENTAL AIR AND VACUUM LINE
 DRAWINGS AND DETAILS INCLUDING PIPING PLANS AND
 SPECIFICATIONS, LOCATIONS OF THE COMPRESSED AIR AND
 VACUUM EQUIPMENT, EQUIPMENT SCHEDULES AND PRODUCT
 SUBMITTALS. CLARIFY IF MEDICAL GAS WILL BE USED AT THE
 FACILITY AND PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS IN ACCORDANCE WITH NFPA 99.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401