| Notes |
| Date |
Text |
| 2021-06-24 16:21:37 | I CANNOT FIND ANY RECORDS OF AN EXISTING MECHANICAL | | | SYSTEM. | | | 1) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE | | | LAYOUT OF THE BUILDING AND THE LOCATION OF THE EXISTING | | | AND NEW MINI SPLITS. | | | 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS AND SHOW ON | | | THE DRAWING HOW THE OUTDOOR AIR IS BEING INTRODUCED | | | INSIDE THE BUILDING. | | | 3) PLEASE PROVIDE ANCHORAGE DETAILS FOR THE OUTDOOR | | | CONDENSING UNITS. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|