Plan Review Notes
Plan Review Notes For Permit 21060673
Permit Number 21060673
Review Stop G
Sequence Number 1
Notes
Date Text
2021-07-06 17:06:5007/06/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P3.1;
 A. THE UNDERGROUND GAS NEED TO HAVE A VENT ON ONE SIDE
 PER THE 2020 G2415.8.1 CONDUIT WITH ONE END TERMINATING
 OUTDOORS.
  
 B. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 C. THE SYSTEM DOES NOT HAVE THE TOTAL BTU'S; THE FUTURE
 IS NOT SHOWN; PLEASE LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE 2020 FBC RES. SEC. G2413. LIST THE BTU LOAD OF
 EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM.
 REFER TO THE 2020 FBC RES. SECS. G2413.3, G2413.4, AND
 TABLES G2413.4 (1) THROUGH G2413.4 (21).
  
 D. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT
 (FUTURE GENERATOR, FIRE PIT, TANK-LESS, AND
 RANGE/OVEN)TO VERIFY COMPLIANCE WITH 2020 FBC RES. SEC.
 G2408.1.
  
 E. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE INSPECTION TIME PER THE 2020 FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 F. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC
 G2421.2.
  
 G. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5.
  
 H. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS.
  
 I. PLEASE SHOW AND LABEL ALL DRIP LEGS ON EQUIPMENT
 INSTALLED, EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD
 GRILLS PER THE 2020 FBC RES. SEC. G2419.2.
  
 J. THE LOCATION OF THE WATER HEATER SHALL COMPLY WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. J. ON THE HOUSE
 PLAN, SHOW THE LOCATION OF THE TANK-LESS WATER HEATER
 AND THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 K. A NOTE MAY BE PLACED ON PLANS. L. PIPES NOT IN
 CONDITION SPACE NEED TO BE INSULATED WITH A MINIMUM R-3
 PER THE 2020 FBC SEC. RE 403.5.3.
  
 L. IF TANK-LEES UNITS ARE CONDENSATION, THEY NEED TO BE
 1' AWAY FROM STRUCTURE PER THE 2020 FBC SEC. R318.5. A
 NOTE MAY BE PLACED ON PLANS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  