2021-07-01 17:39:10ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) GARAGE PANEL TO HAVE MAIN BREAKER INSTALLED PER
 225.33
  
 225.33 MAXIMUM NUMBER OF DISCONNECTS. (A) GENERAL. THE
 DISCONNECTING MEANS FOR EACH SUPPLY PERMITTED BY 225.30
 SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR SIX
 CIRCUIT BREAKERS MOUNTED IN A SINGLE ENCLOSURE, IN A
 GROUP OF SEPARATE ENCLOSURES, OR IN OR ON A SWITCHBOARD
 OR SWITCHGEAR. THERE SHALL BE NO MORE THAN SIX
 DISCONNECTS PER SUPPLY GROUPED IN ANY ONE LOCATION.
  
 2) GARAGE PANEL TO HAVE A GROUNDING ELECTRODE SYSYEM
 INSTALLED 250.33
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S). (A) GROUNDING ELECTRODE.
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH
 PART III OF ARTICLE 250. THE GROUNDING ELECTRODE
 CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN
 250.50 SHALL BE INSTALLED.
  
 3) FOYER TO HAVE OUTLETS INSTALLED PER 210.52 (I)
  
 210.52(I) FOYERS. FOYERS THAT ARE NOT PART OF A HALLWAY
 IN ACCORDANCE WITH 210.52(H) AND THAT HAVE AN AREA THAT
 IS GREATER THAN 5.6 M2 (60 FT2) SHALL HAVE A
 RECEPTACLE(S) LOCATED IN EACH WALL SPACE 900 MM (3 FT)
 OR MORE IN WIDTH. DOORWAYS, DOOR-SIDE WINDOWS THAT
 EXTEND TO THE FLOOR, AND SIMILAR OPENINGS SHALL NOT BE
 CONSIDERED WALL SPACE.
  
  
  