| 2021-07-01 17:39:10 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) GARAGE PANEL TO HAVE MAIN BREAKER INSTALLED PER |
| | 225.33 |
| | |
| | 225.33 MAXIMUM NUMBER OF DISCONNECTS. (A) GENERAL. THE |
| | DISCONNECTING MEANS FOR EACH SUPPLY PERMITTED BY 225.30 |
| | SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR SIX |
| | CIRCUIT BREAKERS MOUNTED IN A SINGLE ENCLOSURE, IN A |
| | GROUP OF SEPARATE ENCLOSURES, OR IN OR ON A SWITCHBOARD |
| | OR SWITCHGEAR. THERE SHALL BE NO MORE THAN SIX |
| | DISCONNECTS PER SUPPLY GROUPED IN ANY ONE LOCATION. |
| | |
| | 2) GARAGE PANEL TO HAVE A GROUNDING ELECTRODE SYSYEM |
| | INSTALLED 250.33 |
| | |
| | 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) |
| | OR BRANCH CIRCUIT(S). (A) GROUNDING ELECTRODE. |
| | BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR |
| | BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR |
| | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH |
| | PART III OF ARTICLE 250. THE GROUNDING ELECTRODE |
| | CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH |
| | 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING |
| | ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN |
| | 250.50 SHALL BE INSTALLED. |
| | |
| | 3) FOYER TO HAVE OUTLETS INSTALLED PER 210.52 (I) |
| | |
| | 210.52(I) FOYERS. FOYERS THAT ARE NOT PART OF A HALLWAY |
| | IN ACCORDANCE WITH 210.52(H) AND THAT HAVE AN AREA THAT |
| | IS GREATER THAN 5.6 M2 (60 FT2) SHALL HAVE A |
| | RECEPTACLE(S) LOCATED IN EACH WALL SPACE 900 MM (3 FT) |
| | OR MORE IN WIDTH. DOORWAYS, DOOR-SIDE WINDOWS THAT |
| | EXTEND TO THE FLOOR, AND SIMILAR OPENINGS SHALL NOT BE |
| | CONSIDERED WALL SPACE. |
| | |
| | |
| | |