| Plan Review Notes For Permit 21060589 |
| Permit Number |
21060589 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-18 17:06:37 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 1609, SEE PAGE 13 OF THE PRODUCT APPROVAL. | | | CRETE FLEX FASTENER INTO A CONCRETE SUBSTRATE REQUIRES | | | A 3" EDGE DISTANCE. SOME PRODUCT APPROVALS ALLOW | | | REDUCTION OF THE MINIMUM EDGE DISTANCE WITH A FACTOR | | | APPLIED (TIGHTER SPACING) BUT I DO NOT SEE THAT OPTION | | | AVAILABLE ON THIS PRODUCT APPROVAL. EITHER REVISE THE | | | INSTALLATION SCHEDULE OR ADVISE WHERE THE PRODUCT | | | APPROVAL ALLOWS A 2.25" MINIMUM EDGE DISTANCE, 6" | | | FASTENER SPACING. |
|