| Plan Review Notes For Permit 21060565 |
| Permit Number |
21060565 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-08-05 15:20:00 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE COMMENTS FROM THE FIRST TWO REVIEWS HAVE NOT | | | BEEN ADDRESSED. SUBMIT THE ACTUAL TEST REPORTS FOR THE | | | SOUND INSULATION THAT YOU WOULD LIKE TO USE. THE | | | PROFLEX MSC REQUIRES AN 8" SLAB WITH A SUSPENDED | | | DRYWALL CEILING. | | | | | | TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S: | | | E-84, E-90 & E-492. | | | FBC 603.1 FLAME SPREAD - ASTM E 84-09 | | | | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | | | | |
|