| 2021-06-28 12:39:00 | 06/28/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE SPECIFICATIONS FOR THE GENERATOR ARE 16KW, AND |
| | THE ONE ON ISOMETRIC IS FOR 27 KW. PLEASE PROVIDE |
| | CORRECT SPECIFICATIONS PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. THE TOTAL BTU LOAD ON THE ISOMETRIC DOES NOT PERTAIN |
| | TO LP; IT IS FOR NATURAL GAS; PLEASE CORRECT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 3. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC |
| | G2421.2. |
| | |
| | 4. THE SEDIMENT TRAP IS SHOWN ON ITS SIDE. IT SHALL BE |
| | INSTALLED VERTICALLY IN THE BOTTOMMOST OPENING OF THE |
| | TEE, AS ILLUSTRATED IN FIGURE G2419.4 OF THE 2020 FBC |
| | RESIDENTIAL GAS. |
| | |
| | 5. ANODES SPECIFICATION IS NOT TOO CLEAR AND BLURRY. |
| | PLEASE PROVIDE SPECIFICATIONS THAT SHOW THE NUMBER OF |
| | MAGNESIUM BAG(S), SIZE, & TYPE OF ANODE CABLE AMOUNT OF |
| | WATER TO ACTIVATE IT. |
| | |
| | 6. THE LP TANK SPECS PROVIDED REFER TO THE 2017 FBC GAS |
| | CODE. PLEASE PROVIDE THE CURRENT CODE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 7. REGULATOR SPEC IS HARD TO READ. PLEASE PROVIDE CLEAR |
| | LEGIBLE COPIES PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS |
| | SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL ON THE |
| | DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE |
| | CODE SEC. 61G15-23.005. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |