| 2021-06-09 09:09:26 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 PROVIDE THE FOLLOWING INFORMATION FOR |
| | MIAMI-DADE COUNTY NOA NO.: 15-1201.09 THE PROPOSED FLAT |
| | ROOF SYSTEM TO BE USED CORRESPONDING TO THE SUBMITTED |
| | ENGINEERS LETTER. COVER PAGE, EVALUATION REPORTS TO |
| | INCLUDE LIMITATIONS PAGE AND INSTALLATION INSTRUCTIONS |
| | FOR SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. |
| | 2. FBC B 107.2.1 REVISE ENGINEER LETTER TO INCLUDE |
| | COMPLIANCE WITH THE 2020 FBC-RESIDENTIAL WIND LOAD |
| | REQUIREMENTS FOR ENHANCED NAILING OF DRIP EDGE, |
| | INSULATION PANELS & BASE SHEETS IN EXPOSURE D CATEGORY |
| | AREAS. LETTER MUST ALSO INCLUDE SYSTEM NO. & PAGE NO. |
| | USED FROM MIAMI-DADE COUNTY NOA NO. 15-1201.09. |
| | |