| 2021-12-11 14:40:09 | NFIP REVIEW |
| | |
| | [email protected] |
| | |
| | 1. THE SURVEYOR DEPICTS THE PARCEL AS AN X ZONE BASED |
| | ON A CLOMR-F. A CLOMR DOES NOT AMEND THE MAP AND THIS |
| | HAS BEEN ACKNOWLEDGED BY THE SURVEYOR. SUBMIT A |
| | CORRECTED SURVEY. |
| | |
| | HTTPS://WWW.FEMA.GOV/GLOSSARY/CONDITIONAL-LETTER-MAP-RE |
| | VISION-CLOMR |
| | |
| | 2. THE FIRST FLOOR SQUARE FOOT AREA IS SHOWN AS |
| | APPROXIMATELY 10,000 SQUARE FEET AND THE UPPER FLOORS |
| | AS APPROXIMATELY 26,000 SQUARE FEET. SEE FLORIDA |
| | BUILDING CODE BUILDING, DEFINITION OF FLOOR AREA. THE |
| | BUILDING AREA IS THE AREA ENCLOSED BY WALLS OR UNDER |
| | THE PROJECTION OF THE ROOF OR FLOOR/CEILING ASSEMBLY |
| | ABOVE. REVISE ACCORDINGLY. THE BUILDING FOOTPRINT IN |
| | OUR GIS/FLOODPLAIN MANAGEMENT FILES WILL BE DETERMINED |
| | BY THE FIRST FLOOR WHICH NEEDS TO BE CONSISTENT WITH |
| | THE BUILDING PLANS. |
| | |
| | |
| | |
| | |
| 2021-12-08 14:33:41 | NFIP REVIEW |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | FLOOD ZONE AE 6 - LOWEST FLOOR ELEVATION WILL NEED TO |
| | BE 8.00 NAVD - ORDINANCE NO. 4729-17 SEC. 18-33 |
| | SURVEY SHOWS FLOOD ZONE "X" WITH A CLOMR - CANNOT |
| | APPROVE WITH A CONDITIONAL LOMR |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) ELEVATION CERTIFICATE PROVIDED IS INCORRECT - BOX |
| | C2(A) SHOULD BE 8.01 AND C2(B) SHOULD BE 8.10 - C2(D) |
| | SHOULD BE 8.01 - OR AS PROPOSED. |
| | |
| | ELEVATION CERTIFICATE INSTRUCTIONS - ITEMS C2.A-D. |
| | ENTER THE BUILDING ELEVATIONS (EXCLUDING THE ATTACHED |
| | GARAGE) INDICATED BY THE SELECTED BUILDING DIAGRAM |
| | (ITEM A7) IN ITEMS C2.A?C.. IF THERE IS AN ATTACHED |
| | GARAGE, ENTER THE ELEVATION FOR TOP OF ATTACHED GARAGE |
| | SLAB IN ITEM C2.D. |
| | |
| | |
| | |