Plan Review Notes
Plan Review Notes For Permit 21060517
Permit Number 21060517
Review Stop NFIP
Sequence Number 4
Notes
Date Text
2021-12-11 14:40:09NFIP REVIEW
  
 [email protected]
  
 1. THE SURVEYOR DEPICTS THE PARCEL AS AN X ZONE BASED
 ON A CLOMR-F. A CLOMR DOES NOT AMEND THE MAP AND THIS
 HAS BEEN ACKNOWLEDGED BY THE SURVEYOR. SUBMIT A
 CORRECTED SURVEY.
  
 HTTPS://WWW.FEMA.GOV/GLOSSARY/CONDITIONAL-LETTER-MAP-RE
 VISION-CLOMR
  
 2. THE FIRST FLOOR SQUARE FOOT AREA IS SHOWN AS
 APPROXIMATELY 10,000 SQUARE FEET AND THE UPPER FLOORS
 AS APPROXIMATELY 26,000 SQUARE FEET. SEE FLORIDA
 BUILDING CODE BUILDING, DEFINITION OF FLOOR AREA. THE
 BUILDING AREA IS THE AREA ENCLOSED BY WALLS OR UNDER
 THE PROJECTION OF THE ROOF OR FLOOR/CEILING ASSEMBLY
 ABOVE. REVISE ACCORDINGLY. THE BUILDING FOOTPRINT IN
 OUR GIS/FLOODPLAIN MANAGEMENT FILES WILL BE DETERMINED
 BY THE FIRST FLOOR WHICH NEEDS TO BE CONSISTENT WITH
 THE BUILDING PLANS.
  
  
  
  
2021-12-08 14:33:41NFIP REVIEW
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 FLOOD ZONE AE 6 - LOWEST FLOOR ELEVATION WILL NEED TO
 BE 8.00 NAVD - ORDINANCE NO. 4729-17 SEC. 18-33
 SURVEY SHOWS FLOOD ZONE "X" WITH A CLOMR - CANNOT
 APPROVE WITH A CONDITIONAL LOMR
  
 CORRECTIONS NEEDED -
  
 1) ELEVATION CERTIFICATE PROVIDED IS INCORRECT - BOX
 C2(A) SHOULD BE 8.01 AND C2(B) SHOULD BE 8.10 - C2(D)
 SHOULD BE 8.01 - OR AS PROPOSED.
  
 ELEVATION CERTIFICATE INSTRUCTIONS - ITEMS C2.A-D.
 ENTER THE BUILDING ELEVATIONS (EXCLUDING THE ATTACHED
 GARAGE) INDICATED BY THE SELECTED BUILDING DIAGRAM
 (ITEM A7) IN ITEMS C2.A?C.. IF THERE IS AN ATTACHED
 GARAGE, ENTER THE ELEVATION FOR TOP OF ATTACHED GARAGE
 SLAB IN ITEM C2.D.
  
  
  