Plan Review Notes
Plan Review Notes For Permit 21060517
Permit Number 21060517
Review Stop M
Sequence Number 1
Notes
Date Text
2021-12-08 08:31:181ST AUDIT FBC-2020 MECHANICAL
 PERMIT-21060517
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN AUDIT RESULTS: DEFICIENIES OBSERVED-
  
 1) THERE ARE REVISION NARRATIVES THROUGH OUT THE
 MECHANICAL DRAWINGS STATED ?ISSUED IN RESPONSE TO CITY
 PLAN REVIEW. THIS IS THE 1ST AUDIT OF THESE PLANS FOR
 THE CITY, PLEASE REWORD THESE NOTES TO STATE THE
 PRIVATE PROVIDER REVISIONS. FBC 107.2.1
  
 2) THE OUTDOOR AIR CALCULATIONS FOR THE LOUNGE AND
 FITNESS CENTER APPEAR TO BE LOW. PLEASE CALCULATE THESE
 AREAS BASED ON FBC M 403.3.1.1 AND TABLE 403.3.1.1.
  
 3) THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF SPACE
 INCLUDING THE CONFERENCE ROOM, BOH AREA AND STORAGE
 AREAS ARE MISSING. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 4) WHERE ARE THE ENCLOSED PARKING GARAGE EXHAUST
 CALCULATIONS; THE CARBON MONOXIDE DETECTOR AND NITROGEN
 DIOXIDE PLAN? FBC M 404.
  
 5) SHEET M3.01: WHERE ARE THE MEASUREMENTS SHOWN ON THE
 DRAWING INDICATING THE EXHAUST LOUVER MEETS THE 3?
 CLEARANCE FROM OPENINGS INTO THE BUILDING? FBC M
 501.3.1
  
 6) SHEET M3.03: WHERE IS THE OUTDOOR AIR DUCT WORK AND
 TERMINATION LOCATION FOR AHU-P3? FBC M TABLE 403.3.1.1
  
 7) SHEET M3.05: WHERE IS THE OUTDOOR AIR DUCT WORK AND
 TERMINATION LOCATION FOR AHU-P4? FBC M TABLE 403.3.1.1
  
 8) SHEET M3.05: WHERE IS THE OUTDOOR AIR DUCT WORK AND
 TERMINATION LOCATION FOR AHU-P4? FBC M TABLE 403.3.1.1
  
 9) SHEET M3.07: WHERE IS THE OUTDOOR AIR DUCT WORK AND
 TERMINATION LOCATION FOR AHU-P5? FBC M TABLE 403.3.1.1
  
 10) WHERE ARE THE RETURN AIR TRANSFER GRILLE SIZES FOR
 EACH MECHANICAL PLAN FOR THE UNITS? FBC M 601.6
 EXCEPTION 2.
  
 11) WHERE ARE THE MEASUREMENTS SHOWING THE EXHAUST
 TERMINATIONS ARE 3 FT FROM OPERABLE OPENINGS INTO THE
 UNITS ON THE UNIT PLANS? FBC M 501.3.1
  
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  