| 2021-12-08 08:31:18 | 1ST AUDIT FBC-2020 MECHANICAL |
| | PERMIT-21060517 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN AUDIT RESULTS: DEFICIENIES OBSERVED- |
| | |
| | 1) THERE ARE REVISION NARRATIVES THROUGH OUT THE |
| | MECHANICAL DRAWINGS STATED ?ISSUED IN RESPONSE TO CITY |
| | PLAN REVIEW. THIS IS THE 1ST AUDIT OF THESE PLANS FOR |
| | THE CITY, PLEASE REWORD THESE NOTES TO STATE THE |
| | PRIVATE PROVIDER REVISIONS. FBC 107.2.1 |
| | |
| | 2) THE OUTDOOR AIR CALCULATIONS FOR THE LOUNGE AND |
| | FITNESS CENTER APPEAR TO BE LOW. PLEASE CALCULATE THESE |
| | AREAS BASED ON FBC M 403.3.1.1 AND TABLE 403.3.1.1. |
| | |
| | 3) THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF SPACE |
| | INCLUDING THE CONFERENCE ROOM, BOH AREA AND STORAGE |
| | AREAS ARE MISSING. FBC M 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 4) WHERE ARE THE ENCLOSED PARKING GARAGE EXHAUST |
| | CALCULATIONS; THE CARBON MONOXIDE DETECTOR AND NITROGEN |
| | DIOXIDE PLAN? FBC M 404. |
| | |
| | 5) SHEET M3.01: WHERE ARE THE MEASUREMENTS SHOWN ON THE |
| | DRAWING INDICATING THE EXHAUST LOUVER MEETS THE 3? |
| | CLEARANCE FROM OPENINGS INTO THE BUILDING? FBC M |
| | 501.3.1 |
| | |
| | 6) SHEET M3.03: WHERE IS THE OUTDOOR AIR DUCT WORK AND |
| | TERMINATION LOCATION FOR AHU-P3? FBC M TABLE 403.3.1.1 |
| | |
| | 7) SHEET M3.05: WHERE IS THE OUTDOOR AIR DUCT WORK AND |
| | TERMINATION LOCATION FOR AHU-P4? FBC M TABLE 403.3.1.1 |
| | |
| | 8) SHEET M3.05: WHERE IS THE OUTDOOR AIR DUCT WORK AND |
| | TERMINATION LOCATION FOR AHU-P4? FBC M TABLE 403.3.1.1 |
| | |
| | 9) SHEET M3.07: WHERE IS THE OUTDOOR AIR DUCT WORK AND |
| | TERMINATION LOCATION FOR AHU-P5? FBC M TABLE 403.3.1.1 |
| | |
| | 10) WHERE ARE THE RETURN AIR TRANSFER GRILLE SIZES FOR |
| | EACH MECHANICAL PLAN FOR THE UNITS? FBC M 601.6 |
| | EXCEPTION 2. |
| | |
| | 11) WHERE ARE THE MEASUREMENTS SHOWING THE EXHAUST |
| | TERMINATIONS ARE 3 FT FROM OPERABLE OPENINGS INTO THE |
| | UNITS ON THE UNIT PLANS? FBC M 501.3.1 |
| | |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |