Plan Review Notes
Plan Review Notes For Permit 21060517
Permit Number 21060517
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-07-07 10:47:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) A FIRE SPRINKLER SYSTEM IS REQUIRED; HOWEVER, THERE
 ARE NO FIRE SPRINKLER DOCUMENTS SUBMITTED. SIMPLY
 STATING SHOP DRAWINGS WILL BE SUBMITTED IS NOT
 ACCEPTABLE WITH THE MASTER PERMIT.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING
 DOCUMENTS.
 (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF
 PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR
 INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING
 PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S
 RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31,
 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE AHJ. THE DOCUMENTS SHALL INCLUDE:
 (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS
 REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A
 RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND
 EXPERIENCE.
 (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY
 STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH
 THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS
 ARE INTENDED TO CONFORM TO.
 (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF
 RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF
 THE SYSTEM.
 (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT
 SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING
 DOCUMENTS.
 (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY
 FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE
 ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE
 STATED PURPOSE OF THESE RESPONSIBILITY RULES.
 (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND
 BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING
 DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR
 CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE
 OF SUCH DOCUMENTS.
 (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN
 ENGINEERING DOCUMENT ONLY FOR INFORMATION OR
 CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO
 ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER
 SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS
 RESPONSIBILITY.
 (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY
 DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST
 ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS.
 (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY
 ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN
 FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC
 AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND
 INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE
 REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES
 WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE
 AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A
 PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR
 AGENCY APPROVAL ACTION ON THE SAME PROJECT.
 SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW
 IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY?NEW
 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08.
  
  
 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION
 ENGINEERING
 DOCUMENTS.
 (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED
 IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE
 WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND
 DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S),
 MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND
 UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE
 SAFEGUARDING OF LIFE, HEALTH OR PROPERTY.
 (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE
 ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND
 COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES
 AND STANDARDS, WHERE AVAILABLE.
 (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A
 SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION
 SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE
 PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT
 AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE
 TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND
 ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT
 SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED
 BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE
 FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL
 BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS.
 (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION
 FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT
 COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED
 ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER
 OF RECORD FOR THE FIRE PROTECTION SYSTEM.
 (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS,
 SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY
 RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN
 ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS,
 UNLESS SHOWN ON OTHER RELATED DOCUMENTS.
 (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER
 OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION
 IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED
 PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE
 SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR
 OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE
 SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED
 4-2-2000, 6-26-01
  
 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION
 SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE:
 (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER
 SUPPLY AS DEFINED BY 633.021(18) F.S.
 (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE
 CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING
 STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND
 CONCLUSIONS.
 (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA.
 (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE,
 DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR
 EACH SEPARATE 42 HAZARD OCCUPANCY.
 (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS
 MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR
 CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE
 NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM
 DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY
 DEMANDING DESIGN AREA.
 (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE
 FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO
 CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION,
 STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH
 RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND
 LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF
 SERVICE.
 (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE
 POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF
 WATER.
 (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF
 RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER
 SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION
 (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE
 LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY
 WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY
 TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND
 THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE
 PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE
 MEASURES.
 (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND
 DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS
 INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.
 (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD
 AND INTERIOR FIRE PROTECTION COMPONENTS.
 (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE
 MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL
 DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING
 APPROVAL AND DOCUMENTATION.
 (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE
 INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE
 OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL
 ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE
 CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED
 4-2-2000, 6-26-01, 7-12-05
  
 FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION
 SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE
 COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING
 DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM
 INFORMATION TO BE PROVIDED ON FIRE PROTECTION
 ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS
 STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP
 THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA
 PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS
 BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER
 SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING
 DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING
 PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED
 FOR THE FIRE SPRINKLER INSTALLATION PERMIT.
  
 PLEASE PROVIDE THE REQUIRED SIGNED AND SEALED
 DOCUMENTATION IN NARRATIVE FORM OR SYSTEM LAYOUT FORM
 MEETING THE ABOVE REQUIREMENTS.
  
 SHOULD THE EOR DEFER TO A QUALIFIED CONTRACTOR, A
 SIGNED LETTER OF DEFERAL IS REQUIRED AND THEN THE
 CONTRATOR IS REQUIRED TO SUBMITT THE FAC REQUIREMENTS
 WITH THIS MASTER.
  
 SHOP DRAWINGS CAN BE DEVELOPED OFF OF THE ABOVE AND
 SUBMITTED FOR APPROVAL PRIOR TO INSTALLATION.
  
  
 2) ELECTRICAL SHEETS - THERE IS A FIRE ALARM SYSTEM
 INDICATED.
  
 ALL FIRE ALARM WORK SHALL BE SUBMITTED UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLIABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
  
 3) CIVIL SHEETS - THERE IS FIRE LINE UNDERGROUND WORK
 INDICATED. ALL FIRE LINE WORK, INCLUDING THE DDCV,
 SHALL BE SUBMITTED UNDER SEPARATE SHOP DRAWINGS. A FIRE
 SPRINKLER SHOP DRAWING WITH THE UNDERGROUND INDICATED
 DOES NOT PERMIT UNDERGROUND WORK.
  
 INSTALL, TEST AND INSPECT PER NFPA? 24 STANDARD FOR THE
 INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR
 APPURTENANCES, 2013 EDITION
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLIABLE NOTE
 OF ACKNOWLEDGEMENT.
  
  
 4) FIRST FLOOR PLAN - THERE ARE INDICATIONS OF BBQ
 GRILLS ON THE POOL DECK, WITHIN 10' OF THE BUILDING,
 UNDER A CANOPY AND ALONG A REQUIRED EXIT PATH.
  
 PER NFPA 1
  
 10.10.6 COOKING EQUIPMENT.
 10.10.6.1 FOR OTHER THAN ONE- AND TWO-FAMILY DWELLINGS,
 NO
 HIBACHI, GRILL, OR OTHER SIMILAR DEVICES USED FOR
 COOKING, HEATING,
 OR ANY OTHER PURPOSE SHALL BE USED OR KINDLED ON ANY
 BALCONY,
 UNDER ANY OVERHANGING PORTION, OR WITHIN 10 FT (3 M) OF
 ANY
 STRUCTURE.
 10.10.6.1.1 LISTED ELECTRIC PORTABLE, TABLETOP GRILLS,
 NOT TO EXCEED
 200 SQUARE INCHES OF COOKING SURFACE, OR OTHER SIMILAR
 APPARATUS
 SHALL BE PERMITTED.
  
 14.3 EXITS.
 14.3.1 WHERE THIS CODE REQUIRES AN EXIT TO BE SEPARATED
 FROM OTHER
 PARTS OF THE BUILDING, THE SEPARATING CONSTRUCTION
 SHALL MEET THE
 REQUIREMENTS OF SECTION 8.2 OF NFPA 101 AND THE
 FOLLOWING:
 (1)* THE SEPARATION SHALL HAVE A MINIMUM 1-HOUR FIRE
 RESISTANCE
 RATING WHERE THE EXIT CONNECTS THREE OR FEWER STORIES.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE JUSTIFICTION WITH
 SPECIFIC CODE REFERENCES.
  
  
  
 5) SHEET A 212 - THERE IS A DOOR, 132L, FROM THE POOL
 DECK TO INSIDE THE PARKING GARAGE, THAT INSWINGS AND
 APPEARS TO ENCROACH THE EXIT PATH.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 PLEASE REVIEW AND CORRECT.
  
  
 5A) SHEET A 212 AND LS SHEETS - DOOR A132L INDICATES
 AND EXIT PASSING INTO AND THRU THE PARKING GARAGE. AN
 EXIT SHOULD NOT PASS THRU AND UNPROTECTED AREA OF
 GREATER HAZARD'
  
 PER NFPA 101
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 A PARKING GARAGE IS A STORAGE OCCUPANCY.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERNECES
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL