| 2021-12-08 14:25:02 | NEW 4 STORY RESIDENTIAL BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING A0.02 THE DRAWING INDEX REVISION DATES NEEDS |
| | TO REFLECT THE MEP REVISION NUMBER 2 DATE. |
| | |
| | 2) PLEASE SHOW THE EXTERIOR WALL FIRE RATING FOR THE |
| | SOUTH ELEVATION WHICH SHOWS 7 FOOT DISTANCE FROM THE |
| | PROPERTY LINE FBC TABLE 602 |
| | |
| | FBC 705.5 FIRE-RESISTANCE RATINGS. |
| | EXTERIOR WALLS SHALL BE FIRE-RESISTANCE RATED IN |
| | ACCORDANCE WITH TABLES 601 AND 602 AND THIS SECTION. |
| | THE REQUIRED FIRE-RESISTANCE RATING OF EXTERIOR WALLS |
| | WITH A FIRE SEPARATION DISTANCE OF GREATER THAN 10 FEET |
| | (3048 MM) SHALL BE RATED FOR EXPOSURE TO FIRE FROM THE |
| | INSIDE. THE REQUIRED FIRE-RESISTANCE RATING OF EXTERIOR |
| | WALLS WITH A FIRE SEPARATION DISTANCE OF LESS THAN OR |
| | EQUAL TO 10 FEET (3048 MM) SHALL BE RATED FOR EXPOSURE |
| | TO FIRE FROM BOTH SIDES. |
| | |
| | FIRE SEPARATION DISTANCE. THE DISTANCE MEASURED FROM |
| | THE BUILDING FACE TO ONE OF THE FOLLOWING: |
| | 1.THE CLOSEST INTERIOR LOT LINE. |
| | 2.TO THE CENTERLINE OF A STREET, AN ALLEY OR PUBLIC |
| | WAY. |
| | 3.TO AN IMAGINARY LINE BETWEEN TWO BUILDINGS ON THE |
| | LOT. |
| | |
| | 3) PLEASE PROVIDE THE CALCULATIONS FOR THE OPENINGS IN |
| | THE EXTERIOR FIRE RATED WALLS - FBC 705.8.1 ALLOWABLE |
| | AREA OF OPENINGS. |
| | THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS |
| | PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A |
| | BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN |
| | TABLE 705.8. |
| | |
| | 4) PLEASE SHOW THE ENCLOSED GARAGE VENTILATION - FBC |
| | 406.6.2 VENTILATION. |
| | A MECHANICAL VENTILATION SYSTEM SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL. |
| | |
| | 5) UNITS S-1, S-2, S-3, A-3 - PLEASE SHOW THE BATHROOM |
| | CLEAR FLOOR SPACE ( TO ALLOW THE DOOR TO BE CLOSED FROM |
| | THE INSIDE) - FBC ACCESSIBILITY FHA REQUIREMENT 7 - |
| | (A)BATHROOMS THAT HAVE REINFORCED WALLS FOR GRAB BARS |
| | (SEE REQUIREMENT 6) WOULD MEET SECTION |
| | 100.205(C)(3)(IV) IF: |
| | (I)SUFFICIENT MANEUVERING SPACE IS PROVIDED WITHIN THE |
| | BATHROOM FOR A PERSON USING A WHEELCHAIR OR OTHER |
| | MOBILITY AID TO ENTER AND CLOSE THE DOOR, USE THE |
| | FIXTURES, REOPEN THE DOOR AND EXIT. |
| | (B)BATHROOMS THAT HAVE REINFORCED WALLS FOR GRAB BARS |
| | (SEE REQUIREMENT 6) WOULD MEET SECTION |
| | 100.205(C)(3)(IV) IF: |
| | (I)WHERE THE DOOR SWINGS INTO THE BATHROOM, THERE IS A |
| | CLEAR SPACE (APPROXIMATELY 2?6" BY 4?0") WITHIN THE |
| | ROOM TO POSITION A WHEELCHAIR OR OTHER MOBILITY AID |
| | CLEAR OF THE PATH OF THE DOOR AS IT IS CLOSED AND TO |
| | PERMIT USE OF FIXTURES. |
| | |
| | 6) ELECTRICAL DRAWINGS SHOW ELECTRICAL VEHICLE CHARGING |
| | STATIONS - PLEASE SHOW THAT AT LEAST 1 OF THE CHARGING |
| | STATIONS IS AN ACCESSIBLE PARKING SPACE, ACCESS AISLE, |
| | SIGNAGE ETC. PER FBC ACCESSIBILITY FHA REQUIREMENT 2 |
| | (4) AND (14) |
| | |
| | 7) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR |
| | DOORS AND ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED |
| | TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING |
| | DESIGNER OF RECORD. FBC WPB 107.3.4 |
| | |
| | 8) ROOFING SYSTEMS, EXTERIOR WINDOW AND DOOR PRODUCT |
| | APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS |
| | TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - FBC WPB |
| | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |