| 2021-06-23 11:11:22 | ****CORRECTIONS**** |
| | |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | THE FOLLOWING ARE REQUIRED PRIOR TO ISSUANCE OF A DEMO |
| | PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303: |
| | |
| | 3) PLEASE PROVIDE THE METHOD OF WATER DOWN DURING |
| | DEMOLITION: |
| | A) IF A WATER TRUCK IS DESIRED, PROVIDE A LETTER |
| | STATING THE GALLON CAPACITY OF WATER TANK AND A |
| | STATEMENT THAT THE WATER USED WILL BE POTABLE WATER |
| | FROM AN OFF?SITE LOCATION ONLY AND THE WATER TRUCK WILL |
| | BE ON?SITE AT ALL TIMES DURING DEMOLITION. |
| | B) IF A HYDRANT METER IS DESIRED THAN A |
| | PERMIT/REGISTRATION NEEDS TO BE OBTAINED FROM THE CITY |
| | OF WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT. |
| | C) IF A BACK FLOW PREVENTER IS DESIRED, THEN A SEPARATE |
| | BACKFLOW PERMIT INCLUDING THE FINAL INSPECTION FROM THE |
| | BUILDING DEPARTMENT (PLUMBING) IS REQUIRED. |
| | IF SELECTING THE BACKFLOW OPTION; BEFORE SCHEDULING THE |
| | FINAL PLUMBING INSPECTION, THE BACKFLOW DEVICE NEEDS TO |
| | BE TESTED AND CERTIFIED BY THE PUBLIC UTILITIES |
| | DEPARTMENT, 561 822 2244. |
| | |
| | 4) THE SEWER LATERAL CAPPING PERMIT HAS BEEN OBTAINED |
| | (21060646). THE APPROVED FINAL PLUMBING INSPECTION IS |
| | REQUIRED. |
| | |