| 2021-07-14 17:36:51 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 21060458 |
| | 7/14/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P1.11 RISER: THE FIXTURE DRAIN FROM THE BATHTUB IN |
| | BATH 2 SHALL CONNECT TO THE HORIZONTAL WET VENT |
| | DOWNSTREAM OF THE LAVATORY FIXTURE DRAIN CONNECTION IN |
| | ORDER TO AVOID CODE VIOLATION OF TWO FIXTURE DRAINS |
| | CONNECTING OF THE DRY VENT CONNECTION TO THE WET VENT- |
| | SECTION P3108.2.1 FBC RES. |
| | |
| | 2) P1.11 RISER: SHOW THE WC AND LAV FIXTURE DRAINS |
| | CONNECTING TOGETHER IN A BRANCH UPSTREAM OF THE STACK |
| | CONNECTION TO THE BUILDING DRAIN- SECTION P3108.1 FBC |
| | RES. |
| | |
| | 3) P1.11: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER |
| | HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- |
| | SECTION P2801.3 FBC P, M2005.1 FBC M, AND C404.1 FBC |
| | EC. |
| | |
| | 4) P1.11: INDICATE HOW THE WATER HEATER WILL BE |
| | PROTECTED FROM VEHICLE DAMAGE- SECTION 305.7 FBC P. |
| | |
| | 5) P1.11: PLEASE SHOW THE DISCHARGE LOCATION OF THE |
| | WATER HEATER RELIEF VALVE DISCHARGE PIPE- FLOOR, PAN, |
| | OR TO THE OUTDOORS- SECTION P2804.6.1 FBC. |
| | |
| | 6) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED |
| | FOR THE NEW HOUSE IRRIGATION SYSTEM- SECTION 105.1 & |
| | 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |