2021-06-25 14:05:571ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21060448
 6/25/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE STEAM
 GENERATOR DRAIN PAN- SECTIONS 502.1 & 802.1.3 FBC P.
  
 2) INDICATE THE TYPE OF WASTE RECEPTOR TO BE INSTALLED
 FOR THE PAN DRAIN LINE AND PROVIDE AN INSTALLATION
 DETAIL- SECTIONS 802.3 & 802.4 FBC P.
  
 3) INSTALLATION OF THE NEW WASTE RECEPTOR MAY REQUIRE
 THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB.
  
 4) THE NEW RECEPTOR DRAIN PIPE PENETRATION OF THE
 EXISTING SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE
 ANNULAR SPACE AROUND THE PIPING. PROVIDE A UL TESTED
 AND APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN-
 SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B.
  
 5) PROVIDE A WATER RISER DRAWING SHOWING THE SUPPLY
 LINE TO THE STEAM GENERATOR AND LOCATIONS OF REQUIRED
 WATER HAMMER ARRESTOR AND BACKFLOW PREVENTER- SECTIONS
 604.9 AND 608.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  