| 2021-07-19 14:08:33 | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE SPECIFICATIONS FOR MAIN DRAINS PER FBC |
| | 454.1.6.;5.10.2. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. REF. PLAN PAGE P1.0 FOR THE FOLLOWING: |
| | CODE REFERENCES 454.1.3.1.2/.6 AND .9 ARE NOT PER |
| | CURRENT 2020 FBC. PLEASE UPDATE THESE CODE REFERENCES. |
| | |
| | 3. PROVIDE SPECIFICATIONS THAT COMPLY WITH THE 2020 FBC |
| | FOR THE CHAIR LIFTS. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 4. REF. PLAN PAGE P1.0 FOR THE FOLLWOING: |
| | PROVIDE STATEMENT THAT THE CHAIR LIFTS SHALL COMPLY |
| | WITH THE 2020 FBC SEC. 1009.2 THRU 1009.9. |
| | |
| | 5. REF. PLAN PAGE P1.1 FOR THE FOLLWING: |
| | P1.1 & P1.2: A COMPLETE REVIEW OF THE REQUIRED PLUMBING |
| | FIXTURE COUNTS FOR THE DAY POOL AND SALT SPA CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO A LACK OF INFORMATION ON |
| | THE PLANS- THE NUMBER OF PLUMBING FIXTURES HAS NOT BEEN |
| | CALCULATED BY THE SQUARE FOOTAGE AREAS OF THE POOL AND |
| | SPA AS REQUIRED BY TABLE 454.16.1 FBC B. BECAUSE |
| | RESTROOM FACILITIES FOR THE DAY POOL AND SALT SPA ARE |
| | BEING PROVIDED BY THE HOTEL BUILDING, PLEASE REVIEW THE |
| | EXCEPTION UNDER SECTION 454.1.6.1.1 FBC B AND PROVIDE: |
| | A) THE FIXTURE REQUIREMENT FOR THE BUILDING. IF IT |
| | EXCEEDS THE REQUIREMENT IN TABLE 454.1.6.1 THEN THE |
| | BUILDING REQUIREMENT SHALL REGULATE THE FIXTURE COUNT, |
| | OTHERWISE THE FIXTURE COUNT SHALL BE BASED ON THE |
| | REQUIREMENT FOR THE POOL. UNDER NO CIRCUMSTANCES SHALL |
| | THE FIXTURE COUNTS BE CUMULATIVE. B) WOMEN'S RESTROOMS |
| | SHALL HAVE A RATIO OF THREE TO TWO WATER CLOSETS |
| | PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER |
| | CLOSETS AND URINALS PROVIDED FOR MEN. LAVATORY COUNTS |
| | SHALL BE EQUAL. |
| | A COMPLETE ACCESSIBILITY REVIEW CANNOT BE PERFORMED AT |
| | THIS TIME. PROVIDE COMPLETE ADA SPECIFICATIONS FOR |
| | SANITARY FACILITIES PER FBC ACCESS. CHPT. 6. |
| | |
| | 6. REF. PLAN PAGE P1.3 FOR THE FOLLOWING: |
| | DECK DRAINS APPEAR TO BE MISSING FOR THE DAY SPA AND |
| | SALT SPA PER FBC 454.1.3.1.2. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| 2021-07-19 14:05:23 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE SPECIFICATIONS FOR MAIN DRAINS PER FBC |
| | 454.1.6.;5.10.2. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. REF. PLAN PAGE P1.0 FOR THE FOLLOWING: |
| | CODE REFERENCES 454.1.3.1.2/.6 AND .9 ARE NOT PER |
| | CURRENT 2020 FBC. PLEASE UPDATE THESE CODE REFERENCES. |
| | |
| | 3. PROVIDE SPECIFICATIONS THAT COMPLY WITH THE 2020 FBC |
| | FOR THE CHAIR LIFTS. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 4. REF. PLAN PAGE P1.0 FOR THE FOLLWOING: |
| | PROVIDE STATEMENT THAT THE CHAIR LIFTS SHALL COMPLY |
| | WITH THE 2020 FBC SEC. 1009.2 THRU 1009.9. |
| | |
| | 5. REF. PLAN PAGE P1.1 FOR THE FOLLWING: |
| | PLUMBING FACILITIES APPEAR TO NOT COMPLY WTH TABLE |
| | 454.1.6.1. WOMEN'S WATER CLOSETS SHALL BE AT A RATIO OF |
| | 3 TO 2 FOR MEN'S WATER CLOSETS AND URINALS COMBINED. A |
| | COMPLETE ACCESSIBILITY REVIEW CANNOT BE PERFORMED AT |
| | THIS TIME. PROVIDE COMPLETE ADA SPECIFICATIONS FOR |
| | SANITARY FACILITIES PER FBC ACCESS. CHPT. 6. |
| | |
| | 6. REF. PLAN PAGE P1.2 FOR THE FOLLOWING: |
| | IDENTIFY LOCATION OF THE DAY SPA AND SALT SPA. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 7. REF. PLAN PAGE P1.2 FOR THE FOLLOWING: |
| | DECK DRAINS APPEAR TO BE MISSING AT THE ADULT POOL PER |
| | FBC 454.1.3.1.2. |
| | |
| | 8. GUTTER SPECIFICATIONS: |
| | GUTTER SPECS ON PG. AP2.0 SPECIFIES A PENTAIR MODEL |
| | GUTTER. DETAIL ON PG. AP2.2 SHOWS A HAYWARD MODEL OF |
| | GUTTER. |
| | PLEASE CLARIFY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |