| 2021-06-24 16:48:44 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21060421 |
| | 6/24/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A3.2: PLEASE PROVIDE THE GRAB BAR |
| | REINFORCEMENT LOCATIONS FOR THE WATER CLOSET AND |
| | SHOWER. SHOW THE MOUNTING HEIGHTS, LENGTHS AND WIDTHS, |
| | AND TYPE OF REINFORCEMENT MATERIALS- SECTIONS 604.5, |
| | 608.3, 609.4 & 609.8 FBC ACC. |
| | |
| | 2) P1.1, P3.1: INDICATE HOW DRAINAGE FROM THE NEW ICE |
| | MAKER WILL BE CONVEYED TO AN APPROVED PLACE OF |
| | DISPOSAL- SECTIONS 413, 414, & 701.1 FBC P. PROVIDE A |
| | DETAIL. |
| | |
| | 3) P2.1 & P3.1: SHOW LOCATIONS OF WATER HAMMER |
| | ARRESTORS AND BACKFLOW PREVENTERS FOR SUPPLY LINES TO |
| | THE DISHWASHER, COFFEE MAKER, ICE MAKER, AND WATER |
| | FILTRATION SYSTEM- SECTIONS 604.9 & 608.3 FBC P. |
| | |
| | 4) P4.1: PROVIDE A DEVICE SCHEDULE THAT INCLUDES THE |
| | WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS, MIXING |
| | VALVE IF TO BE INSTALLED- SECTION 604.9, 607.1.2, & |
| | 608.3 FBC P. |
| | |
| | 5) P4.1 PROVIDE A FULL OPEN VALVE FOR THE SUPPLY LINE |
| | TO THE WATER HEATER- SECTION 503.1 FBC P. |
| | |
| | 6) P0.1 & P4.1: PLENUM RATED WATER SUPPLY AND SANITARY |
| | DRAINAGE PIPING MAY BE REQUIRED WHICH WILL REQUIRE |
| | ADDITIONAL FIRESTOPPING ASSEMBLIES THAT ARE NOT |
| | CURRENTLY PROVIDED- SECTION 315.1 FBC P AND SECTION |
| | 714.4.1.2 FBC B. |
| | |
| | 7) NEW DRAIN PENETRATIONS OF THE SLAB MAY REQUIRE THE |
| | FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING |
| | STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A |
| | NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET- |
| | SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |