| Date |
Text |
| 2021-09-03 09:47:40 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO, CFM |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE SCOPE OF WORK IS STILL NOT CLEAR. PRODUCT |
| | APPROVALS FOR A FIXED WINDOW AND A DOUBLE FRENCH DOOR |
| | WERE SUBMITTED. BASED ON THE FLOOR PLAN IT APPEARS THAT |
| | YOU ARE REPLACING A WINDOW WITH A DOUBLE FRENCH DOOR. |
| | IF THIS IS THE CASE THE PRODUCT APPROVAL FOR THE WINDOW |
| | IS NOT NEEDED. IF ANY WINDOWS ARE TO BE REPLACED, |
| | SPECIFY THEIR LOCATIONS AND SIZES ON THE FLOOR PLAN. |
| | [THE SCOPE OF WORK FOR THE WINDOW AND DOOR IS NOT |
| | CLEAR. PLEASE CLARIFY WHAT YOU ARE PROPOSING TO DO. FBC |
| | AMEND. 107.2.1] |
| | |
| | 2) THE ADDRESS OF THE PROJECT AND THE NAME AND |
| | SIGNATURE OF THE PERSON RESPOSIBLE FOR THE DRAWING ARE |
| | REQUIRED TO BE ON THE PLAN. FBC 107.2.1 - INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. [SUBMIT A FLOOR PLAN THAT SHOWS THE LOCATIONS, |
| | TYPES AND SIZES OF THE WINDOW AND DOOR THAT ARE BEING |
| | REPLACED. FBC AMEND. 107.2.1] |
| | |
| | 3) IF YOU ARE INSTALLING A DOUBLE FRENCH DOOR IN THE |
| | EXISTING OPENING FOR A WINDOW, THE SIZE OF THE OPENING |
| | WILL NEED TO BE INCREASED. SUBMIT A DRAWING WITH |
| | FRAMING DETAILS FOR A WOOD WALL OR BUCK DETAILS FOR |
| | CONCRETE BLOCK WALL. PROVIDE EXTERIOR FLASHING DETAILS. |
| | FBC-R703.4 |
| | |
| | 4) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING AND THE |
| | WIND DESIGN DATA ON THE DRAWINGS. FBC-R301.2.1 |
| | |
| | |
| | |
| | |
| | |