| 2021-07-20 15:11:37 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21060412 |
| | 6/21/21 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1- PLAN PAGE A-1.0 INDICATES A GAS TANKLESS WATER |
| | HEATER IS TO BE INSTALLED IN THE STORAGE UTILITY ROOM. |
| | ON PLAN PAGE P0-1 AN ELECTRIC TANK TYPE WATER HEATER IS |
| | SHOWN. PLEASE CLARIFY. WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 2-- INTERCEPTORS SHALL BE DESIGNED AND SIZED BY THE |
| | GREASE INTERCEPTOR MANUFACTURE. FACTORY SIZING |
| | CALCULATIONS REQUIRED FROM THE MANUFACTURE FBC 2020 P |
| | 1003.2 |
| | 3- THE PLAN PAGE A1.2 INDICATES THE GRAB BARS BEING |
| | MEASURED TO THE CENTER OF THE GRAB BARS. 609.4POSITION |
| | OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, |
| | 4- THE PLAN PAGE A1.2 INDICATES THE MIRRORS ARE NOT |
| | MEASURED 40" TO THE 603.3MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR |
| | 5- A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER |
| | FBCACCESS. SEC. 211.2 & FBC-PLUMBING SEC. 410.3. |
| | 6- PLEASE PROVIDE INFORMATION ON THE BOTTOM LOADING |
| | WATER COOLER |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |