Plan Review Notes
Plan Review Notes For Permit 21060412
Permit Number 21060412
Review Stop P
Sequence Number 2
Notes
Date Text
2021-07-20 15:11:371ST REVIEW FBC-2020 PLUMBING
 PERMIT-21060412
 6/21/21
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- PLAN PAGE A-1.0 INDICATES A GAS TANKLESS WATER
 HEATER IS TO BE INSTALLED IN THE STORAGE UTILITY ROOM.
 ON PLAN PAGE P0-1 AN ELECTRIC TANK TYPE WATER HEATER IS
 SHOWN. PLEASE CLARIFY. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 2-- INTERCEPTORS SHALL BE DESIGNED AND SIZED BY THE
 GREASE INTERCEPTOR MANUFACTURE. FACTORY SIZING
 CALCULATIONS REQUIRED FROM THE MANUFACTURE FBC 2020 P
 1003.2
 3- THE PLAN PAGE A1.2 INDICATES THE GRAB BARS BEING
 MEASURED TO THE CENTER OF THE GRAB BARS. 609.4POSITION
 OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
 4- THE PLAN PAGE A1.2 INDICATES THE MIRRORS ARE NOT
 MEASURED 40" TO THE 603.3MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR
 5- A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 FBCACCESS. SEC. 211.2 & FBC-PLUMBING SEC. 410.3.
 6- PLEASE PROVIDE INFORMATION ON THE BOTTOM LOADING
 WATER COOLER
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  


Account Summary | Usage Policy | Privacy Policy