| 2021-07-20 09:05:19 | |
| | |
| 2021-06-17 08:29:01 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21060412 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE |
| | HOOD AND ANY REFRIGERATION SHALL BE SUBMITTED AS |
| | SEPARATE PERMITS AND WILL REQUIRE SEPARATE REVIEWS. |
| | THEY WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON |
| | FBC 403.3.1.1 AND TABLE 403.3.1.1 AND NOT FROM THE |
| | ARCHITECTURAL OCCUPANT LOAD. |
| | |
| | 403.3.1.1 OUTDOOR AIRFLOW RATE. THE OCCUPANT LOAD |
| | UTILIZED FOR DESIGN OF THE VENTILATION |
| | SYSTEM SHALL BE NOT LESS THAN THE NUMBER DETERMINED |
| | FROM THE ESTIMATED MAXIMUM OCCUPANT LOAD RATE INDICATED |
| | IN TABLE 403.3.1.1. |
| | |
| | 3) MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR RTU-2; |
| | PLEASE CORRECT THE OUTDOOR AIR VENTILATION AIR DATA TO |
| | MEET FBC 403.3.1.1 AND TABLE 403.3.1.1. |
| | |
| | 4) THE MECHANICAL SYSTEMS ARE REFERENCED AS ROOF TOP |
| | UNITS BUT SHEET M2.2 DOES NOT SHOW THE RTU?S ON THE |
| | ROOF. PLEASE PROVIDE CLARIFICATION AS TO WHERE THE |
| | MECHANICAL EQUIPMENT WILL BE LOCATED. FBC 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |