Plan Review Notes
Plan Review Notes For Permit 21060412
Permit Number 21060412
Review Stop M
Sequence Number 1
Notes
Date Text
2021-07-20 09:05:19 
  
2021-06-17 08:29:011ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21060412
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 HOOD AND ANY REFRIGERATION SHALL BE SUBMITTED AS
 SEPARATE PERMITS AND WILL REQUIRE SEPARATE REVIEWS.
 THEY WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 FBC 403.3.1.1 AND TABLE 403.3.1.1 AND NOT FROM THE
 ARCHITECTURAL OCCUPANT LOAD.
  
 403.3.1.1 OUTDOOR AIRFLOW RATE. THE OCCUPANT LOAD
 UTILIZED FOR DESIGN OF THE VENTILATION
 SYSTEM SHALL BE NOT LESS THAN THE NUMBER DETERMINED
 FROM THE ESTIMATED MAXIMUM OCCUPANT LOAD RATE INDICATED
 IN TABLE 403.3.1.1.
  
 3) MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR RTU-2;
 PLEASE CORRECT THE OUTDOOR AIR VENTILATION AIR DATA TO
 MEET FBC 403.3.1.1 AND TABLE 403.3.1.1.
  
 4) THE MECHANICAL SYSTEMS ARE REFERENCED AS ROOF TOP
 UNITS BUT SHEET M2.2 DOES NOT SHOW THE RTU?S ON THE
 ROOF. PLEASE PROVIDE CLARIFICATION AS TO WHERE THE
 MECHANICAL EQUIPMENT WILL BE LOCATED. FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  