2021-06-16 08:45:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) FAULT CURRENT CALCULATION FOR SERVICE AND PANEL NOT
 SHOWN ON PLANS. PLEASE INDICATE THE FAULT CURRENT AT
 THE SERVICE AND PANEL. 110.10, 110.24
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 2) ALL 125V 15, AND 20 AMPERE RECEPTACLES INSTALLED IN
 THE KITCHEN NEED TO BE GFCI PROTECTED. 210.8(B)
  
 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50
 AMPERES OR LESS AND THREEPHASE RECEPTACLES RATED 150
 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS INSTALLED
 IN THE FOLLOWING LOCATIONS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 (2) KITCHENS
  
  