| 2021-09-01 16:14:54 | PLAN REVIEW / NFIP |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 |
| | |
| | 3RD REVIEW CONSTRUCTION DRAWING ELEVATION CERTIFICATE |
| | |
| | NOTICE: |
| | |
| | THE 2-STORY SFR ENCROACHES INTO A SPECIAL FLOOD HAZARD |
| | AREA (SFHA). FLOOD ZONE AE WITH A BASE FLOOD ELEVATION |
| | (BFE) OF 6.0 FEET NAVD. THE DESIGN FLOOD ELEVATION |
| | (DFE) SHALL BE NOT LESS THAN 8.0 FEET NAVD. |
| | |
| | 3 ELEVATION CERTIFICATES (EC) ARE REQUIRED FOR THE |
| | 2-STORY SFR |
| | |
| | THE CABANA AND TERRACE ARE NOT LOCATED IN A SFHA AND DO |
| | NOT REQUIRE EC'S. |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. ELEVATIONS ON PLANS ARE IN NGVD. ELEVATIONS IN |
| | ELEVATION CERTIFICATE ARE IN NAVD 88. A CONVERSION |
| | FACTOR OF 1.519 HAS BEEN PROVIDED. |
| | THIS CONVERSION OF VERTICAL DATUM FROM NGVD TO NAVD |
| | WILL PLACE THE GARAGE FLOOR BELOW THE DESIGN FLOOD |
| | ELEVATION OF 8.0 FT NAVD (9.5 FT NGVD MINUS 1.519 = |
| | 7.981 NAVD). |
| | THIS WILL REQUIRE THE ELEVATION OF THE GARAGE FLOOR OR |
| | THE INSTALLATION OF FLOOD OPENINGS FOR THE GARAGE. |
| | |
| | OPTIONS: 1) CHANGE THE VERTICAL DATUM ON PLANS TO |
| | NAVD88. THIS IS RECOMMENDED. |
| | 2) RAISE THE GARAGE FLOOR .019 FT TO 9.519 NGVD |
| | 3) ENTER CORRECT VALUES IN SECTION A9 (B), (C) AND (D). |
| | INSTALL REQUIRED FLOOD OPENING IN GARAGE. |
| | |
| | 2. BASED ON THE CONVERSION FACTOR, ELEVATION OF C2(A) |
| | TOP OF BOTTOM FLOOR, SHOULD BE 8.481 NAVD AND C2(B) |
| | SHOULD BE 19.781NAVD. C2 (E THRU F) ARE PROPOSED AT |
| | THIS TIME BUT MAY NEED ADJUSTING. |
| | |
| | NOTICE: |
| | |
| | A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS |
| | REQUIRED AT PLACEMENT OF 1ST FLOOR. SUBMIT THIS EC |
| | PRIOR TO COMMENCING WORK. |
| | |
| | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL |
| | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. |
| | NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL |
| | GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE |
| | BUILDING. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |